26
Firmware Upgrade
Note:
(1) The SSH setting on the ATS PDU must be Enabled.
(2) <filename> is the filename of the firmware file. There are
two firmware files to upload: cpsmpdumafw_XXX.bin and
cpsmpdumadata_XXX.bin. In order to upgrade the firmware
version both files need to be uploaded. Only one firmware file
can be uploaded at a time, it is recommended to upload the
firmware file cpsmpdumafw_XXX.bin first followed by the data
file cpsmpdumadata_XXX.bin.
(3) <user> is the username of the SSH account on the ATS PDU.
(4) Ensure to add “:” after the IP address.
5. After executing the command, a message may appear asking if you trust
the host. To continue type "y” for yes within 10 seconds.
6. On the next screen enter the ATS PDU password. The firmware file transfer
may take a couple minutes to complete. Please wait until the progress
indicator displays 100%. The system will automatically log out and reboot
after the transfer is complete.
7. Repeat steps 4 through step 6 to upload the data file cpsmpdumadata_
XXX.bin to complete the firmware update process.
8. If the firmware file transfer is unsuccessful you will see an error message.
Attempt to retype the command and execute it again.
For Linux, MacOS and Unix Users:
1. Install the related distribution of an SSH or SCP client, for example Openssh
client.
2. Open the Terminal and change the path to where the firmware files are
saved.
3. Enter the following command to perform the firmware update:
- pscp –
scp <filename> <user>@<IP address of ATS PDU>:
Note:
(1) The SSH setting on the ATS PDU must be Enabled.
(2) <filename> is the filename of the firmware file. There are
two firmware files to upload: cpsmpdumafw_XXX.bin and
cpsmpdumadata_XXX.bin. In order to upgrade the firmware
version both files need to be uploaded. Only one firmware file
can be uploaded at a time, it is recommended to upload the
firmware file cpsmpdumafw_XXX.bin first followed by the data
file cpsmpdumadata_XXX.bin.
(3) <user> is the username of the SSH account on the ATS PDU.
(4) Ensure to add “:” after the IP address.
For example:
scp cpsmpdumafw_XXX.bin [email protected]:
Note:
cpsmpdumafw_XXX.bin is the firmware file of the version
being updated.
4. After executing the command, a message may appear asking if you trust
the host. To continue type "y” for yes within 10 seconds.
5. On the next screen enter the ATS PDU password. The firmware file transfer
may take a couple minutes to complete. Please wait until the progress
indicator displays 100%. The system will automatically log out and reboot
after the transfer is complete.
6. Repeat steps 3 through step 5 to upload the data file cpsmpdumadata_
XXX.bin to complete the firmware update process.
7. If the firmware file transfer is unsuccessful you will see an error message.
Attempt to retype the command and execute it again.
Troubleshooting
Problem
Possible Cause
Solution
ATS PDU outlets
do not provide
power to connected
equipment
1. Breaker tripped
2. Power cord is not
properly plugged in
Reset Breaker, check the
plug to insure its connected
correctly. If the problem
remains, contact technical
support.
Amperage
displayed on LCD
screen exceeds the
units capability
Overload
The load indicator shows red
when overload. Reduce the
load on the ATS PDU until
the overload is gone. If the
problem remains, contact
technical support.
Circuit breakers
have tripped
1. Sustained overload
2. Excessive ambient
or internal
temperatures
3. Faulty breaker
Reset Breaker.
If the problem remains,
contact technical support.