Part No. 4801-5331 Rev 2-2015
Evolution 1200
35 of 65
** Cool Negative Properties **
These stages typically operate sidewall fans
Since they are not allowed to operate during
Tunnel Ventilation.
(1) Transitional Stage Override = Yes
(2) Override on Stage # 16
7.10 Stage Properties
The Stage Properties screen is where you link to set up specific parameters for the heating and cooling
modes. Stage Properties gives you a definition of how a stage will operate and allows you to add additional
variables to some of the properties.
(1) Heat Properties –
See Section 7.10.1
(2) Cool Stir Properties –
See Section 7.10.2
(3) Cool Negative Properties –
See Section
(4) Cool Negative Tunnel Properties –
See
Section 7.10.4
(5) Cool Tunnel Properties –
See Section
(6) Cool Evaporative Properties -
See Section
(7) Natural Ventilation Properties
- See
Section 7.10.7
7.10.1 Heat Properties
There is one heat property to be setup. Set
to “Yes” if it is desired to operate the heat
stage only during minimum ventilation.
Otherwise the control will allow a heat stage
to operate at the same time a cool stage is
operating if they are looking at different
sensors.
7.10.2 Cool Stir Properties
This allows stir fans to act as mixing fans during
tunnel ventilation.
(1) Allow to operate in Tunnel
– Select Yes or
No.
YES
= The stir fans operate in any
ventilation mode.
NO
= The stir fans will NOT operate during
tunnel ventilation.
7.10.3 Cool Negative Properties
The following parameters can be set:
(1) Transitional Stage Override
– Yes
or No
(2) Override on Stage
– Set to an
available Stage Number.
This feature is used to turn
Cool
Negative Fans
off before entering
tunnel ventilation.
Functionality: When the Override is set (Override on Stage # XX ) to a specific
Cool Negative Tunnel
Stage
, the Stage turns all of the
Cool Negative Fans
OFF when the Stage comes ON.
Example: Turning 36” Sidewall Fans OFF when a 48” Negative Tunnel Fan comes ON while still pulling
air through the vent boards.
** Stage Properties **
(1)Heat Properties
(2)Cool Stir Properties
(3)Cool Negative Properties
(4)Cool Negative Tunnel Properties
(5)Cool Tunnel Properties
(6)Cool Evaporative Properties
(7)Natural Ventilation Properties
** Heat Properties **
Heat Stages operate heating devices
such as heaters or brooders. The
following are additional properties.
Operate during Minimum Vent only = No
** Cool Stir Properties **
These stages typically operate fans
That are used to stir the air inside
The building. They operate in all
Ventilation modes.
(1)Allow to operate in Tunnel = No