Verify if the load cell mounting brackets are securely fastened.
See “Issues with inputs readings”
Verify that the load cell capacity setting match the installed load cells.
The load cell capacity is too small for the size of the bulk feed tank. Replace
with higher capacity load cells.
If you didn’t receive a feed load recently and the tank is not overfilled, the cali-
bration is maybe wrong. Re-calibrate.
If the problem persists, contact AP/Cumberland or GSI Electronics
Calibration pop-up error
message:
Weight distribution tolerance
exceeded
(meaning: too much differ-
ence between legs (load
cells) weight)
The feed weight is not distribute evenly in the bulk feed tank.
Verify if the load cells are free of debris, ice, etc.
Can happen on a windy day or when earth trembles at a passage of a train /
heavy traffic... wait for a more appropriate time to do the calibration
Verify, if so equipped, that the flow hammer on the tank is not running.
Did you receive feed at the moment of calibration? Wait until the filling is termi-
nated and re-calibrate.
Did auger run at the moment of calibration? Wait until the feeding is terminated
and re-calibrate.
See “Issues with inputs readings”
Increase the weight distribution tolerance % in the calibration process. NOTE:
doing this might affect the weight accuracy.
If the problem persists, contact AP/Cumberland or GSI Electronics
Calibration pop-up error
message:
Calibration sensitivity
exceeded input [value] weight
fluctuates by more than
[value]
(meaning: load cell weight
reading varies too much)
Verify if the load cells are free of debris, ice, etc.
Can happen on a windy day or when earth trembles at a passage of a train /
heavy traffic... wait for a more appropriate time to do the calibration
Verify if the load cell mounting brackets are securely fastened.
Verify, if so equipped, that the flow hammer on the tank is not running.
Did you receive feed at the moment of calibration? Wait until the filling is termi-
nated and re-calibrate.
Did auger run at the moment of calibration? Wait until the feeding is terminated
and re-calibrate.
See “Issues with inputs readings”
Increase the calibration sensitivity % in the calibration process. NOTE: doing
this will affect the weight accuracy.
If the problem persists, contact AP/Cumberland or GSI Electronics
Calibration pop-up error
message:
Calibration sensitivity
exceeded. Tank weight varies
by more than [value]
(meaning: Bulk feed tank
weight reading varies too
much)
Verify if the load cells are free of debris, ice, etc.
Can happen on a windy day or when earth trembles at a passage of a train /
heavy traffic... wait for a more appropriate time to do the calibration
Verify, if so equipped, if the flow hammer on the tank is not running.
Verify if the load cell mounting brackets are securely fastened.
Verify, if so equipped, that the flow hammer on the tank is not running.
62
891–00577
EDGE Bin Scale 3 Wires LC
Summary of Contents for 074-11772
Page 26: ...NOTES 26 891 00577 EDGE Bin Scale 3 Wires LC...
Page 34: ...Chapter 3 Basic connections Figure 3 3 Loadcell Wiring 34 891 00577 EDGE Bin Scale 3 Wires LC...
Page 38: ...NOTES 38 891 00577 EDGE Bin Scale 3 Wires LC...
Page 48: ...Chapter 6 Setup Figure 6 2 Tank group setup screen 48 891 00577 EDGE Bin Scale 3 Wires LC...
Page 59: ...891 00577 EDGE Bin Scale 3 Wires LC 59...
Page 64: ...NOTES 64 891 00577 EDGE Bin Scale 3 Wires LC...
Page 66: ...NOTES 66 891 00577 EDGE Bin Scale 3 Wires LC...
Page 68: ...NOTES 68 891 00577 EDGE Bin Scale 3 Wires LC...
Page 78: ...NOTES 78 891 00577 EDGE Bin Scale 3 Wires LC...
Page 80: ...NOTES 80 891 00577 EDGE Bin Scale 3 Wires LC...
Page 82: ...NOTES 82 891 00577 EDGE Bin Scale 3 Wires LC...
Page 84: ...NOTES 84 891 00577 EDGE Bin Scale 3 Wires LC...
Page 88: ...NOTES 88 891 00577 EDGE Bin Scale 3 Wires LC...
Page 90: ...NOTES 90 891 00577 EDGE Bin Scale 3 Wires LC...
Page 94: ...NOTES 94 891 00577 EDGE Bin Scale 3 Wires LC...
Page 100: ...NOTES 100 891 00577 EDGE Bin Scale 3 Wires LC...