GH DRIVER
5-
42
Function
code
Name
Description
Setting
scope
Unit
Factory
setting
Change
Recommend
motor
Pn. 10
Temperature
protection
selection
0: temperature switch
1: Temperature resistance pt3c
2: Temperature resistance kty84
3: Temperature resistance Pt100
9: Shielding
0~9
-
0
○
Synchronous/
Asynchronous
Pn. 11
Temperature
channel selection
Thermistor / temperature switch channel
selection: when multi-channel is selected, the
temperature of U2 group motor is displayed
according to the maximum temperature, and
is selected by bit:
Bit0:1 channel
Bit1: 2 channels
Bit2: 3 channels
Bit3: 4 channels
If there is no selection, it is configured
according to 1 channel
0~65535
-
1
○
Synchronous/
Asynchronous
Pn.12
Motor temperature
sensor alarm value
0: shield, do not detect motor temperature
Others: alarm e1.oh2 when the detected
temperature exceeds this value
0~200
degree
110
○
Synchronous/
Asynchronous
Pn. 13
Motor overspeed
alarm value
0: shielding, do not detect motor feedback
speed
Others: alarm e1.os when motor feedback
speed exceeds this value
0~30000
RPM
8500
○
Synchronous/
Asynchronous
Pn. 14
Motor stall alarm
value
0: shielding, do not detect motor feedback speed
Others: when the motor feedback speed exceeds
this value alarm, when the difference between the
motor feedback speed and the output speed is
greater than (output speed)
Pn.14), and the duration exceeds Pn.15 alarm e1.se
0~100.0
%
40
○
Synchronous/
Asynchronous
Pn. 15
Stall alarm
detection time
0~3000.0
S
4
○
Synchronous/
Asynchronous
Pn. 16
The position follow-
up error overrun
threshold L
0: shielding, no position follow-up error is
detected
Others: alarm e1.op when position follow-up
error exceeds this value
0 ~
4294967295
pulse
0
○
Synchronous/
Asynchronous
Pn. 17
The position follow-
up error overrun
threshold H
Pn. 18
Low speed
overload alarm
speed value
0: shielding, do not detect motor feedback
speed
Others: when the motor feedback speed is lower
than pn.18, and the actual current exceeds
pn.20 dn.01, and the duration exceeds pn.19,
the alarm will be sent to e1.ol2
0~6000.0
RPM
5
○
Synchronous/
Asynchronous
Pn. 19
Low speed
overload alarm time
threshold
0~3000.0
S
2
○
Synchronous/
Asynchronous
Pn.20
Low speed
overload alarm
current multiple
0~100.0
-
1.2
○
Synchronous/
Asynchronous
Pn. 21
Motor overload
protection gain
Motor overload protection parameters, can
change the protection of the inherent curve
sex
0.20
~10.00
-
1
○
Synchronous/
Asynchronous