fig. 15 The control unit
LTALW7H000023
Manufacturer
Sit Controls
Supply voltage
230 V - 1ph - 50 Hz
Pre-purge time
3 s
Post-purge time
5 s
Ignition time
2.5 s
Safety time
5 s
Anti-cycling time
3 till 10 min.
Fuse value F1 (230 V)
2 AT
DC fan
24 VDC
table 04 Control unit characteristics
Any loads other than those specified above are only allowed if an isolating
transformer is used.
page 17
The output of the Remeha Avanta can be controlled in the following ways:
1.
On/off control - volt free switching
- The boilers internal control will
modulate the output to achieve the flow temperature set point of the boiler.
This contact is on the X9 terminal strip (low voltage only).