fig. 52 Checking the combustion
59970LTGBW7H025
Ensure that the analysing probe has a gas tight seal in the sampling point with the
probe end in the centre of the flue duct.
Checking values O
2
/CO
2
for natural gas
Boiler-
type
Fan speed (rpm)
O
2
CO
2
Full load
[H][3]
Part load
[L][3]
%
%
12v
approx. 2400
approx. 1300
5.2 ± 0.2
8.8 ± 0.3
15v
approx. 3000
approx. 1300
5.2 ± 0.2
8.8 ± 0.3
18v
approx. 3500
approx. 1300
5.2 ± 0.2
8.8 ± 0.3
24v
approx. 4500
approx. 1300
5.2 ± 0.2
8.8 ± 0.3
30v
approx. 5200
approx. 1300
5.2 ± 0.2
8.8 ± 0.3
table 10 Checking values O
2
/CO
2
(front panel not fitted)
Checking values O
2
/CO
2
for LPG (propane)
Fan speed (rpm)
O
2
CO
2