fig. 09 Connecting CH flow
59970.LT.GB.W7H.007
page 12
2.3.12 Connecting condensate drain
•
Connect the condensate drain outlet
to a suitable waste water drain point
using acid resisting pipe work (i.e. - ¾" overflow). To enable the siphon in the
boiler to be removed / serviced, the connection should not be a permanent
one (i.e. "push fit" system or a "tundish" immediately below the boiler).
•
To prevent the risk of freezing connect the condensate into an internal vertical
soil pipe using a tundish (air break) c/w a min 75 mm water seal trap.
•
If the condensate pipe has to run externally make sure this is done by
realizing the shortest possible route, and increase the diameter to at least 1¼"
or insulate it with weather resistant insulation.
•
The drain should slope at least 3 cm per meter, with a maximum horizontal
length of 5 m.