fig. 23 Wiring diagram DHW calorifier sensor or thermostat
R000194-A
2.7.7 Connecting a three-way valve
If required a 230 V DIVERTING three-way valve can be connected to terminal X5 of
the control unit. When used in conjunction with an "Open Therm" compensator the
DHW-production operates with priority.
Connector X5-1 for N (neutral), connector X5-2 for "open valve to DHW" (port A of
three-way valve) and connector X5-3 for "open valve to CH" (port B of three-way
valve)
If port A is connected to heating and port B to hot water X5-3 should be
used to enable DHW.
The cable must be fed through the boiler's casing by means of the supplied cable
gland and run trough the cable clamp on the right-hand inside of the boiler.
fig. 24 Wiring diagram three-way valve
R000160-A
2.7.8 Connecting a frost thermostat
The boiler must be installed in a frost-free area to prevent the condensate drain from
freezing. However if the temperature of the CH water in the boiler drops too low, the
integrated boiler protection device is activated as follows:
- at a water temperature below 7°C: the circulation pump is switched on;
- at a water temperature below 3°C: the boiler is switched on;
Summary of Contents for Avanta 12v
Page 34: ...fig 16 Connecting external controls R000158 A page 18 ...
Page 35: ......
Page 63: ...fig 42 Read out settings LT AL W7H 000 046 ...
Page 68: ...fig 43 Change parameters in service level LT AL W7H 000 047 ...
Page 70: ...fig 44 Change boiler output LT AL W7H 000 048 ...
Page 87: ...fig 59 Assembling the boiler 59970LTGBW7H031 page 44 4 ERRORS 4 1 General ...
Page 96: ......
Page 99: ...fig 62 Exploded view Remeha Avanta 59970EVGBW7H010 ...
Page 108: ...page 60 ...
Page 109: ...page 61 ...