Boiler parameters
Water heater parameters
Ref.
Parameter description
Adjustment range
Default
value
Individual burner
(mod. 60T and
70T)
Burner 1 (Master)
(mod. 100T,
115T, 140T, 180T,
210T and 280T)
Burners from
2 to 4
(mod. 100T,
115T, 140T, 180T,
210Tand 280T)
Individual burner
(mod. 60T and
70T)
Burner 1 (Master)
(mod. 100T, 115T,
140T, 180T, 210T
and 280T)
Burners from
2 to 4
(mod. 100T, 115T,
140T, 180T, 210T
and 280T)
Customised
values
3001 Burner operation address
0 = Not in cascade
1 = Burner 1 (Master),
2to4=Burnerfrom2to4(slaveburners)
2
0
1
from 2 to 4
0
1
from 2 to 4
3002 Fan adjustment range
from 0 to 4
0
60 = 0
70 = 2
100 and 115 = 0
140, 180, 210 and 280 = 2
60 = 0
70 = 2
100 and 115 = 0
140, 180, 210 and 280 = 2
3003 Display unit of measurement
C = °C and bar;
F = °F and PSI;
C
C
C
C
C
C
C
3004 Water pressure switch
0 = Disabled; 1 = Enabled;
2 = N/A; 3 = N/A
1
1
1
0
1
1
0
3005
Burner flapper valve
0 = Disabled; 4 = Enabled;
8 = N/A; 12 = N/A
4
0
4
4
0
4
4
3006
Water flow rate sensor
0 = Disabled; 16 = N/A;
32 = N/A; 48 = Enabled
48
48
48
48
48
48
48
3007 Condensate level sensor
EnAb = Enabled;
dISA = Disabled
Enab
Enab
Enab
dISA
Enab
Enab
dISA
3008 Combustion gas sensor type
SEnS = Sensor; StCH = Switch
SEnS
SEnS
SEnS
SEnS
SEnS
SEnS
SEnS
3009 External sensor type
10 = 10kohms; 12 = 12kohms;
10
10
10
10
10
10
10
3010 Other sensor type
10 = 10kohms; 12 = 12kohms;
10
10
10
10
10
10
10
3011
pump mode
0 = main c pump; 1 = N/A;
2 = N/A; 3 = N/A;
0
0
0
0
0
0
0
3012 domestic hot water operating mode
0 = only heating;
1= hot water storage tank;
2 = storage tank with
thermostat;
3 = N/A; 4 = N/A; 5 = N/A
0
0 = only
heating;
1= hot water
storage tank;
0 = only
heating;
1= hot water
storage tank;
0
0 = only
heating;
1= hot water
storage tank;
0 for
instantaneous
domestic hot
water;
1 per hot water
storage tank.
0
3013 Reset Err 115
EnAb = Enabled;
dISA = Disabled
Enab
Enab
Enab
Enab
Enab
Enab
Enab
3015 Climatic adjustment: heating supply
maximum temperature (this parameter
is overwritten by parameter 3017)
from 20°C to 90°C
82°C
82°C
82°C
82°C
N/A
N/A
N/A
3016 Climatic adjustment: heating supply
minimum temperature
from 20°C to 90°C
20°C
20°C
20°C
20°C
N/A
N/A
N/A
3017 Supply maximum temperature (this
parameter takes priority with respect to
parameter 3015)
from 20°C to 90°C
82°C
82°C
82°C
82°C
82°C
82°C
82°C
3018 Minimum supply temperature
from 20°C to 90°C
32°C
32°C
32°C
32°C
32°C
32°C
32°C
3020
Water flow rate sensor type
0 = N/A; 1 = DN8;
2 = DN 10; 3 = DN 15;
4 = DN 20; 5 = DN 25
3
4
4
4
4
4
4
3022 Water minimum pressure
from 0 to 5 bar
1
1
1
1
1
1
1
3035
Minimum water flow rate
from 0 to 100 l/min
27
27
27
27
27
27
27
3050 Slave burner number
from 0 to 3
3
3
100, 115 and
140 = 1
210 = 2
280 = 3
3
3
100, 115 and
140 = 1
210 = 2
280 = 3
3
3085 Modbus address
0 to 126
1
1
1
1
1
1
1
3086 Number of Stopbits
1 or 2
1
1
1
1
1
1
1
3100 Material selection
ABS; CPVC; PVC; SST; PP.
PVC
PVC
PVC
PVC
PVC
PVC
PVC
3101 Nation Selection
US, CA
US
US
US
US
US
US
US
Switch
“S4”
Switch “S4” position (see fig 17-11 and
17-12)
On or Off
On
On
On
Off
On
On
Off
N/A = Not Applicable
ATTENTION!!!
Editing these parameters
could cause the appliance and, therefore, the system
to malfunction. For this reason, only professionally
qualified technicians with in-depth knowledge and
awareness can edit them.
ATTENTION!!!
When accessing the forced
menu, it is possible for the appliance to start up;
ignoring this could cause damage to persons, animals
or objects.
ATTENTION!!!
In the event of the multi-burner
appliances (100T to 280T models), the display is always
connected to burner 1 (MASTER). To set the parameters
in the other burners, the display must be connected to
them as described in section 17.8
The forced menu allows the appliance to be set based
on the system to serve. Setting occurs by adjusting the
available parameters (shown in the table).
To access the forced menu, proceed as follows:
1.- Power off the appliance by turning the main switch to the
OFF position;
2.- Holding down the RESET and
keys at the same
time, turn the main switch to the ON position;
3.- Wait for the word “INIT” or the
3000
parameters to
appear on the display.
4.- Using the
and
keys, scroll through the
list of
3000
parameters;
5.- Navigate the menu using the
and
keys. Once you have selected the parameter, press
the RESET key to make it editable via the
and
keys;
6.- Press the RESET key to save the changes;
7.- Wait 10 seconds;
8.- Power off the appliance;
9.- Repower the appliance to exit the forced menu and go
back to its normal operation.
19 - FORCED MENU