63
60T - 280T
COSMOGAS
16 - USE
Loc 20
Flame lost three times
Make sure: that the ionisation current is at a value
higher than 4 (follow the procedure in section 17.12)
Make sure: that the flue exhaust is appropriately
protected from obstructions caused by gusts of wind
If the ionisation current is not over 4, you must check the
CO2 (follow section 15.8) and restore the proper value.
Check the ionisation glow plug and, if necessary, replace
it. Make sure the ionisation current electrical circuit cables
are intact.
If the flue exhaust is positioned on a vertical wall,
it must be protected by a windproof grid. If the flue
exhaust is positioned on the roof, make sure it is not
in a reflux area and that the windproof chimney, if any,
is actually efficient.
Loc 21
Software error inside
command board
Replace the command and control board
Loc 22
Software error inside
command board
Replace the command and control board
Loc 23
Software error inside
command board
Replace the command and control board
Loc 24
Software error inside
command board
Replace the command and control board
Loc 25 (*) Gas valve circuit
A - Check whether the heating supply safety thermostat
has tripped;
B - Check whether the flue exhaust temperature safety
fuse has tripped;
ATTENTION !!! If the flue exhaust
temperature safety fuse trips, you must contact
the appliance manufacturer to avoid serious
damage to the exchanger.
Loc 26
Software error inside
command board
Replace the command and control board
Loc 27
Flame with gas valve
closed
Replace the gas valve
Loc 28
Flame with gas valve
closed
Replace the gas valve
Loc 29 (*) Interlock input
A - Check LWCO connection;
B - Check flue blocked pressure switch;
A - If LWCO intervenes, try to reset it.
B - Check if flue gas line is free from any blockage
Loc 30
Software error inside
command board
Replace the command and control board
Loc 31
Flame lost three times
A - Check the detection electrode;
B - Make sure that the flue exhaust is appropriately
protected from obstructions caused by gusts of wind.
C - Check for any flue exhaust recirculation
A - Try replacing the detection electrode.
B - Check for and, if necessary, remove any
obstructions from the air intake and flue exhaust ducts;
C - Find the cause of the flue exhaust recirculation
Loc 32
Software error inside
command board
Replace the command and control board
Loc 33
Software error inside
command board
Replace the command and control board
Loc 34
Software error inside
command board
Replace the command and control board
Loc 35
Software error inside
command board
Replace the command and control board
Loc 36
Software error inside
command board
Replace the command and control board
Loc 37
Software error inside
command board
Replace the command and control board
Loc 38
The flue exhaust sensor
temperature does not
rise when the burner
ignites
a-make sure the flue gas sensor meets the require
-
ment in section 17.14.
b - Make sure that the flue gas sensor (parameter
1006) increases the temperature when the burner
ignites.
a-If the flue gas sensor does not meet section 17.14,
it must be replaced.
b - If the temperature does not rise, replace the flue gas
temperature sensor or the command and control board.
* This error stops all the burners