PoolWarden Manual www.poolwardentraining.com 530-205-4520 34
ManualTime 00:02:00
Day of Week smtWtfs
Off If Time < 10:00:00
Off If Time > 12:00:00
On Time
00:30:00
MinTimeOff
00:30:00
Off if Flow Off - 1
Aux1 Feed Daily Selected
⧫
MinTimeOff 00:02:00:
This is the total amount of time the relay will be OFF if the Temperature reaches
the set-point and the relay has been on at least the MinTimeOn. The default setting is 2 Minutes. This
command works in conjunction with the MinTimeOn Command above. This prevents the heater from
kicking on and off frequently if the temperature is fluctuating around the set-point. Never set this time to
00:00:00, that will keep the timers from properly resetting.
⧫
Off if Flow Off - 1:
This Aux1 Relay will be turned off if “No Flow” is detected in Flow Switch Input 1.
Pool1 uses Flow Switch Input 1 and Pool2 uses Flow Switch Input 3. Never allow the heater to turn on if
there is no flow. The heater will have it’s only flow detection which will also keep that from happening.
⧫
Overfeed 10:00:00:
The Overfeed time represents the maximum amount of time a Heater can be on in
a 24-Hour period from midnight to midnight. Calculate the maximum amount of total time the heater
would be on in a 24-Hour period and enter the time here. The default time of 10:00:00 will most likely not
be correct. This will prevent the Heater from continuously running if something goes wrong with the
temperature sensor.
Feed Daily Control Type
Feed Daily can be used to turn on a piece of equipment at the same time every day of the week that or
specific days. It can be used to perform the following:
❑
Turn on at a specific time and off at a specific time
❑
Can be enabled for any or all days of the week
❑
When it is on, it can also cycle on and off
❑
Can be disabled based on a flow switch being off
⧫
Manual Time 00:02:00
: The manual time for any relay can be set up
to 23:59:58.
⧫
Day Of Week smtwtfs
: This is the ON Command for this control
type, if all letters for the days of the week are left lower case, the relay
will not turn on. To enable the relay to turn on select the Day of Week
command and press
Enter
, then select numbers 1 through 7 representing Sunday through Saturday
and toggle between the lower case and uppercase letter of the week. Lower case is disabled and
uppercase means the relay will be enabled or turned on on that day of the week.
⧫
Off If Time < 00:00:00
: This is a modifying command to the Day Of Week Setting and is where the relay
will be off if the time of day is less than the configured time setting. The default setting is zero “00:00:00”
or disabled. Enter the time based on 24-Hour Military Time and press
Enter
to save.
⧫
Off If Time > 00:00:00
: This is a modifying command to the Day Of Week Setting and is where the relay
will be off if the time of day is greater than the configured time setting. The default setting is zero
“00:00:00” or disabled. Enter the time based on 24-Hour Military Time and press
Enter
to save.
⧫
On Time 00:00:00
: This command is used to cycle the relay on and off continuously. Enter the desired
on time for the cycle (such as 2 Hours or 02:00:00) and press
Enter
to save the setting.
⧫
MinTimeOff 00:00:00
: When the relay is going to cycle on and off during the on portion of the day this
command controls how long it will be off. Once this off time has been reached the relay will turn back on
for the On Time. If this cycling feature is going to be used do not leave either the On Time or the
MinTimeOff at 0, they are used together for proper operation.
⧫
Off if Flow Off - 1
: The relay will be turned OFF if “No Flow” is detected in Flow Switch Input 1. Press
Enter to cycle between Flow Switch 1, 2, 3, 4 and none.
Example
: The commands listed in the above box for this section will have Aux1 cycling on for 30 minutes,
and off for 30 minutes on Wednesday between 10AM and noon.