40
Unidrive M300/HS30 Quick Start Guide
Issue Number: 7
RFC-A:
If this parameter is set to 1, the flux is reduced so that the magnetizing current is equal to the torque
producing current, to optimize copper losses and reduce iron losses in the motor under low load
conditions.
If the drive is to be configured in fixed boost mode (Pr
41
= Fd or SrE) with catch a spinning motor
software enabled, an autotune (see Pr
38
on page 43) must be carried out to measure the motor's
stator resistance beforehand. If a stator resistance is not measured, the drive may trip on OV or
OI.AC while trying to catch a spinning motor.
This parameter selects the function of Digital Input 5 (terminal 14).
33
Catch a Spinning Motor
RW
Txt
US
OL
Ú
dis (0), Enable (1), Fr.Only (2),
Rv.Only (3)
Ö
dis (0)
RFC-A
Pr 33
Text
Function
0
dis
Disabled
1
Enable
Detect all frequencies
2
Fr.Only
Detect positive frequencies only
3
Rv.Only
Detect negative frequencies only
34
Digital Input 5 Select
RW
Txt
US
OL
Ú
Input (0), th.Sct (1), th (2),
th.Notr (3), Fr (4)
Ö
Input (0)
RFC-A
Value
Text
Function
0
Input
Digital input
1
th.Sct
Temperature measurement input with short circuit detection
(Resistance <50
Ω
)
2
th
Temperature measurement input without short circuit detection but
with
th
trip
3
th.Notr
Temperature measurement input with no trips
4
Fr
Frequency input