BB2-7030 User Guide – Rev. 1.0
Page 20
Maps entered on this page only write data to remote devices. Go to the Client Read Map to read
data from those devices. The full parameter set is different for read versus write.
An abbreviated version of a list of maps is shown on this page. Any of the parameters shown
may be changed here and registered by clicking the Update button. To view and/or modify the
complete set of parameters, click on the map number in the left most column.
Data from the local object given will be multiplied by the scale factor before being written. For
each remote object to be written, enter the object instance and type, and location (device). The
names in the device list are defined in the Devices page. The name is optional and used only for
display purposes.
Selecting "none" for remote type effectively deletes the map even though it will still appear in
the list until deleted. Unused maps at the end of the list will always show none as the type.
Local Object is internally a coded number consisting of BACnet object type multiplied by 1000,
then added to the object number starting from #1. These are translated into abbreviations that are
easy to interpret on the web page as follows:
AI n = Analog Input #n
AO n = Analog Output #n
AV n = Analog Value #n
BI n = Binary Input #n
BO n = Binary Output #n
BV n = Binary Value #n
MI n = Multi-state Input #n
MO n = Multi-state Output #n
MV n = Multi-state Value #n
Object numbers start at #1. The maximum available number varies by object type, and these
limits may be found on the System Capacities link from the home/index page (click graphic at
top).