BB2-7030 User Guide – Rev. 1.0
Page 32
An abbreviated version of a list of rules is shown on this page. Any of the parameters shown may
be changed here and registered by clicking the Update button. To view and/or modify the
complete set of parameters, click on the map number in the left most column.
For each remote register to be read, enter the register type, format, number, and location
(device). The names in the device list are defined in the Devices page.
When the remote register is read, the data will be multiplied by the scale factor and written to the
local object number given. The name is optional and used only for display purposes.
Selecting "none" for remote type effectively deletes the rule even though it will still appear in the
list until deleted. Unused rules at the end of the list will always show none as the type.
Local Object is internally a coded number consisting of BACnet object type multiplied by 1000,
then added to the object number starting from #1. These are translated into abbreviations that are
easy to interpret on the web page as follows:
AI n = Analog Input #n
AO n = Analog Output #n
AV n = Analog Value #n
BI n = Binary Input #n
BO n = Binary Output #n
BV n = Binary Value #n
MI n = Multi-state Input #n
MO n = Multi-state Output #n
MV n = Multi-state Value #n
Object numbers start at #1. The maximum available number varies by object type, and these
limits may be found on the System Capacities link from the home/index page (click graphic at
top).