BB2-7030 User Guide – Rev. 1.0
Page 13
The source of data for an Analog Input object will be reading an object in another BACnet
device, or receiving of data from a Modbus (or SNMP) device. The device link will point to a
BACnet client read map or a Modbus (or SNMP) client read map.
Out of Service means any polling of the slave device will stop. While out of service, the present
value may be written by the BACnet client. Data may be forced via this web page at any time,
but will be overwritten by the next poll unless the object is out of service.
Reliability codes may be any of the following (7030-01):
64: Modbus client, no response
65: Modbus client, crc error
66: Modbus exception, illegal function code
67: Modbus exception, illegal data address
68: Modbus exception, illegal data value
69-79: Modbus exception, code+65, rarely used
80: Local device, configuration property fault
81: Faulty Modbus packet
82: BACnet IP client, device timeout
83: BACnet IP client, error returned by server
Reliability codes may be any of the following (7030-02):
80: Local device, configuration property fault