BB2-7030 User Guide – Rev. 1.0
Page 6
3.
Minimum
BB2
7030
Gateway/Router
Setup
The BB2-7030 requires only minimal configuration to be useful in its simplest form. First, you
must assign a device instance to the BB2-7030, and you do this via the BACnet IP Port page.
You may leave all other settings at their default. You could leave the device instance at its
default as well. The only real requirement is that you do not duplicate device instances.
The hardware will effectively prevent you from duplicating the MAC address on the IP side, but
you do need to select a MAC address for the MS/TP side of the router. Enter that MAC address
at the bottom of this page. The MAC addresses must not be duplicated on the network. Enter
your MS/TP baud rate and Max Master setting as well.
The second page that contains a minimum requirement is the Network Info page, under the
BACnet Router tab. The network info strings are just that, information only, and are optional.
The network numbers, however, are mandatory
.