set.
BO #3
4003
BO #100
4100
Binary Value Object
Read/written as a single
holding register, any non-zero
value written will result in bit
set.
BINARY VALUE
Object
Modbus Registers
BV #1
5001
BV #2
5002
BV #3
5003
BV #100
5100
Multi-state Input Object
Read/written as single holding
register, treated as unsigned
16-bit integer.
MULTI-STATE INPUT
Object
Modbus Registers
MI #1
13001
MI #2
13002
MI #3
13003
MI #300
13300
Multi-state Output Object
Read/written as single holding
register, treated as unsigned
16-bit integer.
MULTI-STATE OUTPUT
Object
Modbus Registers
MO #1
14001
MO #2
14002
MO #3
14003
MO #100
14100
Multi-state Value Object
Read/written as single holding
register, treated as unsigned
16-bit integer.
MULTI-STATE VALUE
Object
Modbus Registers
MV #1
19001
MV #2
19002
MV #3
19003
MV #100
19100
8. Configuring BB2-7010 as a Modbus RTU Slave