Enter the 8-character hexadecimal MAC address of the sensor whose data is to be received. Select local
BACnet objects where data from channels 1 through 4 of the sensor should be stored. BACnet objects
should be either Analog Input or Analog Value. Do not use any other object type.
Enter a sensor timeout in minutes. If the BB2-7010-07 does not receive data from this sensor within this
amount of time, the BACnet object's reliability property will be set to the non-zero error code indicating
timeout. In addition, the optional timeout fault value will be placed into the object's present value property
if selected on the extended setup page.
To access aditional setup parameters, click on the sensor number in the first column. This will take you to
the extended setup page illustrated below.