the device. The number will range from 300 to 1000 depending on model.
The number displayed next to the input window is the object count that has been requested and will take
effect upon the next restart. To request a different number, enter that number and click Save. Restart (or
power cycle) the device to make the new object allocations take effect.
The check box for "allow fault self-reset without ack" means object reliability code and fault status will
return to normal automatically after recovery from a communication fault such as "no response" (reply
timed out). If this box is not checked, a BACnet client must read the reliability code to acknowledge the
problem before the status will be reset. If the box is checked, fault indications will simply go away when
the fault goes away.
The check box for "enable BBMD" is used to enable the BBMD feature of the device. When enabled,
additional configuration on the BBMD tab should also be set up.
3. Minimum BB2-7010 Gateway Setup