Gsm Advanced Manual - 25
25
25
25
TEMPERATURE
°Celsius °Fahrenheit
SET
VALUE
NTC
[Kohm]
VOLTAGE
[V]
SCALE
FACTOR
1 34,00 261
26,130
2,613
10,0
2 36,00 250
25,030
2,503
10,0
3 37,00 240
23,990
2,399
10,0
4 39,00 230
23,000
2,300
10,0
5 41,00 221
22,050
2,205
10,0
6 43,00 212
21,150
2,115
10,0
7 45,00 203
20,300
2,030
10,0
8 46,00 195
19,480
1,948
10,0
9 48,00 187
18,700
1,870
10,0
10 50,00 180
17,960
1,796
10,0
11 52,00 172
17,240
1,724
10,0
12 54,00 166
16,560
1,656
10,0
13 55,00 159
15,900
1,590
10,0
14 57,00 153
15,280
1,528
10,0
15 59,00 147
14,690
1,469
10,0
16 61,00 141
14,120
1,412
10,0
17 63,00 136
13,580
1,358
10,0
18 64,00 131
13,060
1,306
10,0
19 66,00 126
12,560
1,256
10,0
20 68,00 121
12,090
1,209
10,0
21 70,00 116
11,630
1,163
10,0
22 72,00 112
11,200
1,120
10,0
23 73,00 108
10,780
1,078
10,0
24 75,00 104
10,380
1,038
10,0
25 77,00 100
10,000
1,000
10,0
26 79,00
96
9,632
0,963
10,0
27 81,00
93
9,281
0,928
10,0
28 82,00
89
8,944
0,894
10,0
29 84,00
86
8,622
0,862
10,0
30 86,00
83
8,313
0,831
10,0
31 88,00
80
8,014
0,801
10,0
32 90,00
77
7,728
0,773
10,0
33 91,00
75
7,454
0,745
10,0
34 93,00
72
7,192
0,719
10,0
35 95,00
69
6,940
0,694
10,0
36 97,00
67
6,699
0,670
10,0
37 99,00
65
6,467
0,647
10,0
38 100,00
62
6,245
0,625 10,0
39 102,00
60
6,032
0,603 10,0
40 104,00
58
5,827
0,583 10,0
11.1.7 Example
+5,281,,Probe,83,180,0100,,C,ambient temperature
Set probe input to detect alarm when temperature falls below 10 and rise above 30 (Celsius
degrees defined at index 289), units shown: C
+5,281,,Probe
Disable any alarm detection on probe input.
+5,282,,AuxI,,0,0010,,,burner lockout
Set AuxI in digital mode, reacting to contact opening.
+5,282,,AuxI
Disable any alarm detection on aux input.
11.1.8 Confirmation
Once Phonebook edit has been successfully done, device will send back an SMS specifying
assigned index, name and 7 markers to specify which fields are defined (
*
) and which don’t (
-
):
281,Probe,-****-*
281,Probe,--**--*
282,AuxI,-------
282,AuxI,-------