Ratio Mode
The desired process ratio set point
(RATIO %) is set via the front panel or
serial communications.
The PI controlled output signal is used to
maintain the desired process flowrate via the
proportional control valve.
The desired process flow is determined as a
ratio of the main flow (0 to 400% range) i.e.
Blend-1 Mode
The desired blending ratio set point
(RATIO %) is set via the front panel or
serial communications.
The PI controlled output signal is used to
maintain the desired process flowrate via the
proportional control valve.
The desired process flow is determined as a
ratio of the net (combined) flow (0 to 80%
range). i.e.
Blend-2 Mode
The desired blending ratio set point
(RATIO %) is set via the front panel or
serial communications.
The PI controlled output signal is used to
maintain the desired process flowrate via the
proportional control valve.
The desired process flow is determined as a
ratio of the main (net) flow (0 to 80%
range). i.e.
Main Flow
Proportional
Control Valve
Frequency
Input 1
Process Flow
Flowmeters
Analog
Output
Frequency
Input 2
Ratio
%
P
flow
M
flow
-------------- 100
=
Main Flow
Proportional
Control Valve
Frequency
Input 1
Process Flow
Flowmeters
Analog
Output
Frequency
Input 2
Ratio
%
P
flow
M
flow
P
flow
+
---------------------------------- 100
=
Main Flow
Proportional
Control Valve
Frequency
Input 1
Process Flow
Process
Analog
Output
Frequency
Input 2
Flowmeter
Main
Flowmeter
Ratio
%
P
flow
M
flow
-------------- 100
=
Summary of Contents for 515 BR03
Page 8: ...viii 515 BR03 15 August 2021...
Page 10: ...x 515 BR03 15 August 2021...
Page 16: ...Introduction 6 515 BR03 15 August 2021...
Page 78: ...Instrument Calibration 68 515 BR03 15 August 2021...
Page 100: ...90 515 BR03 15 August 2021...
Page 106: ...96 515 BR03 15 August 2021...