DC Wiring
976-0043-01-01
3–17
Dual Inverters
To ground a dual inverter configuration:
1. Connect the ground bond in the DC disconnect between the inverters
and the batteries to the primary grounding electrode, in accordance
with local and national electrical codes.
2. Connect the NEGATIVE (–) terminal of the battery bank to the
ground bond inside the DC disconnect.
3. Connect an appropriately sized GROUND wire from the Chassis
Bonding Lug on the L1 inverter DC end to the ground bond inside the
DC disconnect.
4. Connect an appropriately sized GROUND wire from the Chassis
Bonding Lug on the L2 inverter DC end to the ground bond inside the
DC disconnect.
Figure 3-8
DC Grounding of Dual Inverters
Summary of Contents for SW 2524
Page 2: ......
Page 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Page 24: ...xxii...
Page 26: ...xxiv...
Page 82: ...2 48...
Page 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Page 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Page 126: ...3 44...
Page 132: ...4 6...
Page 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Page 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Page 143: ...Menu Map 976 0043 01 01 5 11...
Page 144: ...Navigation 5 12 976 0043 01 01...
Page 145: ...Menu Map 976 0043 01 01 5 13...
Page 146: ...Navigation 5 14 976 0043 01 01...
Page 208: ...7 36...
Page 240: ...8 32...
Page 268: ...B 10...
Page 286: ...C 18...
Page 290: ...D 4...
Page 294: ...E 4...
Page 316: ...I 6...
Page 319: ...Index 976 0043 01 01 IX 3...
Page 320: ...Index IX 4 976 0043 01 01...
Page 321: ......