Menu Item Descriptions
976-0043-01-01
6–9
11B Low Battery Cut In VDC
This menu item sets the battery voltage level that turns the inverter back
on after being shut down by the LBCO setting. Set this voltage level
lower than the Bulk or Float volts DC setting.
This voltage level is used to indicate that the batteries have a sufficient
level of charge for the inverter to start using power from the battery bank.
11C Low Battery Cut Out VDC
When the batteries discharge to the level set in
11C Low Battery Cut
Out VDC
, and are held at or below this level for the
11D LBCO Delay
time, the inverter output shuts down and transfers any available AC
source (generator or grid) to the charger to bring the battery level back up
to the
11B Low Battery Cut In Vdc
level. The inverter will not support
any AC loads when in this condition. AC loads will have to be powered
by either a generator or grid power. This is the lowest voltage level
acceptable for battery use by the inverter.
11D LBCO Delay Minutes
Menu item
11D LBCO Delay Minutes
is used to set the length of time
(in minutes) that the inverter is allowed to continuously operate at or
below the LBCO level set in menu item
11C Low Battery Cut Out
before it shuts off.
Once the inverter has shut off, the battery voltage must rise above the
value (set in menu
11B Low Battery Cut In
) for inverter operation to
resume.
Guidelines for setting this menu item:
•
If using an automatic generator starting system, do not set this delay
period shorter than the amount of time it takes the generator to start
and connect. Otherwise, the power will go OFF and then back ON
when the generator auto-starts due to the LBCO condition.
11B Low Battery
Cut In VDC
11C Low Battery
Cut Out VDC
11D LBCO Delay
Minutes
Summary of Contents for SW 2524
Page 2: ......
Page 3: ...Sine Wave Plus Inverter Charger Owner s Manual...
Page 24: ...xxii...
Page 26: ...xxiv...
Page 82: ...2 48...
Page 105: ...DC Wiring 976 0043 01 01 3 23 Figure 3 13 DC Connections to a Single Inverter...
Page 107: ...DC Wiring 976 0043 01 01 3 25 Figure 3 14 DC Connections to Dual Inverters...
Page 126: ...3 44...
Page 132: ...4 6...
Page 139: ...Menu Map 976 0043 01 01 5 7 Figure 5 4 User Menu Map Part 2...
Page 141: ...Menu Map 976 0043 01 01 5 9 Figure 5 6 Basic Setup Menu Map Part 2...
Page 143: ...Menu Map 976 0043 01 01 5 11...
Page 144: ...Navigation 5 12 976 0043 01 01...
Page 145: ...Menu Map 976 0043 01 01 5 13...
Page 146: ...Navigation 5 14 976 0043 01 01...
Page 208: ...7 36...
Page 240: ...8 32...
Page 268: ...B 10...
Page 286: ...C 18...
Page 290: ...D 4...
Page 294: ...E 4...
Page 316: ...I 6...
Page 319: ...Index 976 0043 01 01 IX 3...
Page 320: ...Index IX 4 976 0043 01 01...
Page 321: ......