9
Product Overview
Condair TE
When operation is ceased via pressing of the operation button, an OFF external command signal input,
or similar, water supply will be stopped and only the fan will continue operating. After the humidification
module has been dried by the fan in this manner, the unit will automatically shut off.
Drying operation of the humidification module takes approximately 2 hours. Generally, the drying process
activates for 2 hours after the unit stops humidifying. However; if the humidifier operates continuously
for 24 hours without a 2-hour drying period, the drying process will activate automatically.
3.1.1 Remote Controller
The humidifier must be used with the remote controller. The remote controller contains a humidistat, and
is used to control up to ten units at once. For more information on the remote controller and how to use
it to humidify the space, refer to
“Operator Interface” on page 10
POWER
HUMID.
HIGH
LOW
DRYING
MODE
ALARM
Figure 3: Remote Controller