38
Appendix
Condair TE
A
Appendix
A.1
Start-up Checklist
Refer to this checklist and the installation manual to ensure safe and proper use of the humidifier.
The humidifier main unit is level (check using a level tool) and firmly fixed in place.
Supply water piping ring joints are securely attached and annealed copper tube contains no kinks,
breakages or similar.
Hose bands are securely attached to the drain hose, the drain piping is installed with a downward
gradient of 1:100 or greater, and no obstruction obscures the flow path.
If using a raised-section drainage piping configuration, a vinyl chloride pipe or a hose is used, and
the raised piping section does not exceed 31.5 in (800 mm) in height (max. 47.2 in (1200 mm) from
the ceiling surface).
All electrical wiring is correctly installed and secured.
The control unit DIP switch is set in the correct positions.
There is no gap or misalignment between the grille frame and ceiling panels.
The ceiling inspection hatch is installed in the correct position (in a manner that does not hinder
maintenance operations for piping and other components).
Sufficient flushing has been carried out for the supply water piping.
Open water supply service valve.
Supply the humidifier with power.