18
Operation
Condair TE
5.7.4 Changing the Humidity Setpoint with the Remote Controller
The set humidity level can be adjusted in 5% increments between 35% and 70% RH.
The default setting is 40% RH. To check the current setpoint, refer to section
To change the humidity setpoint:
1. Turn off the humidifier and ensure that the power light is off on the remote controller.
2. Press and hold the side button on the remote controller for 3 seconds. The power light will illuminate
green.
3. Press the side button 1 time. The power light turns off. The humidification light will illuminate green.
4. Press the FAN, STOP, or FIND button on the remote controller to toggle the lights on the remote
controller. The humidity setpoint corresponds to the light combinations in
5. Once the humidity level is set, save the setting by pressing the side button 1 time. The high fan light
will illuminate orange. The remote controller powers off when the process completes.
Table 6: Setting the humidity setpoint with the remote controller
Light
Combination
Push to toggle light
ON or OFF
Humidity Setpoint RH
- light off
○ light on
35 %
40 %
45 %
50 %
55 %
60 %
65 %
70 %
High
FAN
-
-
-
-
-
-
-
-
Low
-
-
-
-
○
○
○
○
Drying mode
STOP
-
-
○
○
-
-
○
○
Error
FIND
-
○
-
○
-
○
-
○
5.7.5 Changing the Humidity Detection Sensitivity
Humidity detection sensitivity can be toggled between two levels: high and low. The default detection
sensitivity is high; this detection sensitivity level can be used without changing any settings.
To change the humidity detection sensitivity:
1. Turn the humidifier off and ensure that the power lights on the remote controller are OFF.
2. Press and hold the side button on the remote controller for 3 seconds. The power light turns green.
3. Press the FIND button to toggle between low and high sensitivity.
•
An illuminated alarm light indicates low sensitivity.
•
An absent alarm light indicates high sensitivity (default).
4. Press the side button 2 times to save your setting. The high indicator light illuminates orange for 3
seconds. The remote controller powers off once the process is complete.
5.8
Checking the Current Settings on the Remote Controller
Specific combinations of lights on the remote controller indicate the settings on it. The check begins with
the setup of the humidifier, then the humidity setpoint.
To check the settings:
1. Turn off the humidifier and ensure that the power light is off on the remote controller.
2. Press the side button. The check will complete in 20 seconds, then the remote controller will power off.
a. The power light will illuminate green for 10 seconds. During this time, other lights on the remote
controller will illuminate. Refer to the combinations in the table below.