29
Important!
Use original Condair steam hose exclusively. Other types of steam hoses can cause
undesired operational malfunctions.
The following notes must be observed:
– Lead the steam hose with an
upslope of at least 20%
or with a
minimum downslope of 5%
to
the steam distribution pipe.
– The steam hose should be kept as short as possible (
ideally 2 m, max. 4 m
) while observing the
minimum bend radius of 300 mm
.
Important!
Allowance must be made for a
pressure loss
of 10 mm water column (approx. 100 Pa)
per meter steam hose.
– Reductions in the cross section such as kinks should be avoided throughout the entire length of
the hose. The installation of a stop cock in the steam hose is not permissible.
– Steam hoses must be prevented from sagging (condensate pockets); if necessary, support with
pipe clamps, rails or wall brackets. If sagging can not be prevented (e.g. when passing by obsta-
cles) a condensate drain with siphon (min. hose bend Ø200 mm) must be mounted at the lowest
point of the steam hose (see following illustration).
min. 5 %
min. 20 %
min. 20 %
max. 4 m
Rmin.
300 mm
5.3.3 Installing the steam hoses between steam hose adapter
and steam distributors
–
Important!
When deciding on the length and layout of the hose, it should be noted that the steam
hose may become somewhat shorter with progressive ageing.
R min. 300 mm
min. 20 %
min. 5 %
max. 4 m