67
9
Troubleshooting
9.2
Error indication
Malfunctions during operation are indicated by a corresponding warning message (operation still pos-
sible, red LED flashes) or a fault message (operation not possible any longer, red LED lights) in the
display of the operating and control unit. Detailed information thereto can be found in the separate
operating instructions for Condair GS control.
9.1
Important notes on troubleshooting
Qualification of personnel
Have faults eliminated by
adequately qualified and trained personne
l only.
Malfunctions caused by
the electrical installation must be repaired by authorized personnel (e.g. electrician) only.
Safety
When eliminating faults, the Condair GS
must be taken out of operation
, as described in chapter
7.5, and prevented from further inadvertent operation.
Make sure the power supply to the unit is cut off (test with voltage tester) and that the stop
valves in the water and gas supply line are closed.
General note
Most operational malfunctions are not caused by faulty equipment but rather by improper installa-
tion or disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves a
thorough examination of the entire system. Often, the steam hose connection has not been properly
executed, or the fault lies with the humidity control system.
9.3
Resetting the error indication
To reset the error indication:
Disconnect the Condair GS from the mains for approx. 5 seconds, then reconnect again.
Note: If the fault has not been eliminated, the error indication reappears after a short while.