5. Pre-purge of the gas pressure regulating valve(s):
• Disconnect all ignitors from the ignition modules.
• Switch-On the humidifier at the unit switch.
The combustion air blower will pre-purge for 0 seconds. After 15 seconds the gas pressure
regulating valve opens for 4 seconds, then it closes again. After three tries the humidifier goes
into safety lockout.
Note: To reset the safety switch-off, switch-off the humidifier for at least five seconds and then
switch it on again.
Repeat this sequence minimum 2 times in order to make sure no air is left in the gas sy-
stem.
• Switch-off the humidifier at the unit switch.
• Reconnect all ignitors to the ignition modules.
6. Start the humidifier:
• Open the shut-off valve in the water supply pipe.
• Open the shut-off valve in the gas supply pipe.
• Switch on the external service switch.
• Switch the humidifier On at the unit switch.
The Condair GS carries out a
system and level test
, during which all the
LEDs light up.
If a failure occurs on the system test, a corresponding error message is
shown in the display.
After the system test the unit is in
normal operation mode
. The display shows
the
standard operating display
(first page of the indication level).
Note: The contents of the standard operating display depends on the actual
operating status and on the configuration of the Condair GS and can differ
from the opposite display.
As soon as the humidity controller demands humidity, the auto ignition
activates the igniter. This heats up and after approx. four seconds the gas
pressure regulating valve opens. The burner ignites and steam is gene-
rated in the tank via the heat exchanger(s). The green LED lights and the
adjacent display is shown.
If no flame is detected by the flame sensor within three seconds of the igni-
tion, the gas pressure regulation valve closes again. The ignition sequence
is repeated a maximum of three times, after which the humidifier goes
into system lockout. The red LED lights and an appropriate fault message
appears in the display. At the same time, the operating and remote fault
alarm potential-free contact (“Error”) closes.
Note: The system lockout is reset by switching the humidifier off briefly (5
seconds) and then on again.
Condair GS 240
START UP
Menu
Condair GS 240
Standby
03.03.2009 12.00.00
Menu
Condair GS 240
Demand :50%
03.03.2009 12.05.00
Note:
for detailed information regarding the operation of the control unit and the configuration set-
tings please observe the information given in the
separate operating instructions to the Condair
GS control
.