background image

 

Section 1 

An Introduction to Dielectric Withstand Testing with the HT-PR 

 
The continuity test/dielectric withstand test is a production line test which is recognized by safety 
agencies worldwide as a valid criterion of safe assembly of end-use equipment.  The test ensures 
that the primary circuit power and ground conductors were properly wired and connected for safe 
operation.  It also applies a high-voltage potential between power and ground conductors to make 
sure  that  no  unintentional  leakage  or  arcing  paths  exist  between  power  and  ground.    The  test 
consists  of  a  ground  continuity  check,  a  leakage  current  check  and  a  high  voltage  check.    It  is 
non-destructive to the equipment under test, and can be accomplished in a short time. 
 
The  purpose  of  dielectric  testing:    Dielectric  testing  is  a  simple,  non-destructive  method  of 
verifying  the adequacy of electrical insulation to withstand the sort of transients that can occur 
during  transient  (surge)  events.    In  addition,  the  dielectric  test  can  verify  that  the  insulation  in 
question has an adequate amount of performance "headroom".  This is necessary to ensure that 
the insulation does not fail because of degradation of the insulation due to aging, moisture, wear 
due to vibration, etc. 
 
The  method  of  dielectric  testing:    A  high  voltage  (typically  1000  Volts  or  higher)  is  applied 
between two conductors that are "supposed" to be electrically insulated from each other.  If the 
two  conductors  (an  insulated  "live"  wire,  and  a  metal  enclosure,  for  example)  are  completely 
isolated  from  each  other,  then  the  application  of  a  large  voltage  difference  between  the  two 
conductors  will  not  allow  current  to  flow  between  the  conductors.    The  insulation  will 
"withstand" the application of a large voltage potential between the two conductors - hence the 
term "dielectric withstand test".   In general, there are two results of the test that are considered a 
failure  of  the  insulation:    (1)  excessive  current  flow  during  the  test  due  to  low  insulation 
resistance  of  the  insulating  material  which  separates  the  two  conductors,  and  (2)  an  abrupt 
dielectric breakdown due to electrical arcing or discharge, either through the insulation material, 
over the surface of the insulation material, or a discharge through air. 
 
The determination of a suitable test voltage:  If the test voltage is too low, the insulation material 
in  question  will  not  be  adequately  stressed  during  the  test.    This  could  cause  inadequate 
insulation to pass the test, and be considered acceptable.  On the other hand, if the test voltage is 
too high, then the test could cause permanent damage to an insulation material that is otherwise 
adequate  for  the  application.    A  general  "rule  of  thumb"  that  is  used  for  the  testing  of  mains 
wiring which operates at voltages of 120-240Vac is 1000V plus two times the operating voltage.  
Using this rule, 120V wiring would be tested using a voltage of 1240Vac. 
 
Duration of the test:  Generally, the test voltage is applied for one minute, in order to adequately 
stress  the  insulation.    Many  standards  allow  the  test  duration  to  be  reduced  to  1  second  for 
production-line  testing  in  order  to  accommodate  large-volume  production  testing.    In  this  case, 
standards quite often require that the test voltage be increased by 20% in order to ensure that the 
shorter test duration of one second will adequately test the insulation in question 
 
The following figure show the most common application of this tester, in this kind of devices the 
three  different  test  are  perform,  the  ground  connection  between  the  exposed  metal  or  Chassis 
with  the  grounding  pin  of  the  power  supply,  the  insulation  and  leakage  current  between  the 
primary power and the ground pin of the device are verified. 

Summary of Contents for HT-2000PR

Page 1: ...tand Tester HT 2000PR AC only with Ground Continuity Check HT 2800PR DC only with Ground Continuity Check HT 3000PR AC DC with Ground Continuity Check 0 2000 Volts AC Output 0 2800 Volts DC Output Ins...

Page 2: ......

Page 3: ...ogic controlled circuit design and ergonomic front panel and represents the latest in high voltage production line testing To fully appreciate all the features of your new meter we suggest that you ta...

Page 4: ...ii...

Page 5: ...Requirements 12 Fuse Replacement 13 Front and Rear Panel Features 13 Initial checkout procedure 18 Test Verification procedure when using the HTT 1 function checker 18 Performance Test Using cables 19...

Page 6: ...iv Voltage Calibration Adjustment 33 Current Calibration Adjustment 34 Ground Resistance adjustment 35...

Page 7: ...1...

Page 8: ...l between the two conductors hence the term dielectric withstand test In general there are two results of the test that are considered a failure of the insulation 1 excessive current flow during the t...

Page 9: ...ing to conduct the dielectric withstand test They should understand electrical fundamentals clearly and be aware that high voltage is adept and creative at completing a path to ground Instructions sho...

Page 10: ...feature and should not be defeated unless two wire products are being tested In that event it is imperative that the operator make absolutely sure the Test Return Lead is properly connected to the equ...

Page 11: ...ection is absent the exposed dead metal of your product could be at line potential indefinitely after an internal wiring fault causing risk of shock to anyone touching it To make sure that the measure...

Page 12: ...he chassis has a resistance higher than the indicated in the ground setting This indicates a problem with the connection of the HT PR to the equipment being tested or that the ground connection in the...

Page 13: ...akage current level up to 20 mA AC HT 2000PR HT 3000PR or 5mA DC HT 2800PR HT 3000PR The leakage current trip level is adjustable on the rear panel The leakage test is conducted by shorting the line a...

Page 14: ...nt on the capacitors of the circuit the test should now be successful High Voltage Dielectric Withstand Test This test checks for insulation system breakdowns between the primary and ground circuits T...

Page 15: ...r use on a 15 amp branch circuit in North America For other types of products a different receptacle type or pigtail leads may be required Various adapters and pigtail leads are available from Complia...

Page 16: ...buzzer sounds and any voltage stored in the equipment being tested is bled off by a resistor bank in the HT PR The voltage discharge progress is shown by the front panel meter Failure modes are shown...

Page 17: ...ustments Rear Panel Ramp Time Test Time Leakage Limit Voltage Adjust Ground Offset Tamper proof operation available by removing adjustment shafts ENVIRONMENTAL Operating Temperature 15 40 C Relative H...

Page 18: ...AWG Line Power Cord to provide power to the HT PR This Instruction Manual If reshipment of the instrument is necessary please use the original shipping container If the original shipping container is...

Page 19: ...2 Unplug the instrument from the source of supply 3 Remove the power inlet cord from the instrument 4 Using a small screwdriver pry open the fuse holder door 5 Replace the fuse with a new one of the c...

Page 20: ...14 Figure 3 Controls Indicators Connectors Model HT 3000PR Front Panel...

Page 21: ...ll be terminated 5 Full Voltage LED If full voltage is successfully reached the Full Voltage LED will light and the high voltage duration timer starts 6 Hipot Fail LED Indicates failure of high voltag...

Page 22: ...16 Figure 4 Controls Indicators Connectors HT PR Rear Panel...

Page 23: ...Voltage Test Duration section for this procedure 5 Leakage Limit Adjustment Used to adjust the trip level for the excessive leakage current test See Leakage Current Level on Adjustment section for mor...

Page 24: ...by the HT PR is exposed during this test A risk of shock exists Exercise care when using the HT PR Performance Test Using the HTT 1 Function checker Recommended This section describes how the HT PR is...

Page 25: ...oper source of supply using the included 18 AWG power supply cord Turn the HT PR ON 2 Turn the Ground Check switch on the rear panel to the OFF position 3 Disconnect all test leads 4 Push the red RESE...

Page 26: ...ST button 21 The tester should conduct a test sequence terminated with a buzzer At test termination the Ground OK Ground Open Excess Leakage and red RESET LED s should be lit see figure 6 test result...

Page 27: ...from service and contact Compliance West USA Inc for servicing information Figure 6 Expected results for performance test Insulation Leakage current Ground Switch R value Test Result Good I I Setting...

Page 28: ...ime 1 second High Voltage Level 1800 Volts High Voltage Test Time 2 seconds Ground resistance 1 50 Table 6 Factory settings Adjustments of the various settings are shown below CAUTION High voltage is...

Page 29: ...st 30 seconds use the procedure of the High Voltage Test Time 3 Connect the HT PR to a correctly rated source of supply and turn the power switch to the I or ON position Push the RESET button The yell...

Page 30: ...d increments from 1 to 60 seconds 3 If tamperproof settings are desired the Test time Limit control shaft may be pulled away with a slight tug It may be reinserted for future adjustments Figure 10 Tes...

Page 31: ...ton is pressed the voltage will ramp and hold Adjust the Ramp Time control on the rear panel see figure 4 until the desired ramp time is reached The test can be terminated at any time by pressing the...

Page 32: ...witch controls whether the Ground Test is conducted between the chassis and the power supply cord grounding pin of the unit being tested The safety agencies require that this test be conducted on all...

Page 33: ...est USA also offers the models HTT 1 and HTT 1R which can be used to quickly verify the operation of your HT PR Contact the factory for details Connections This section describes the most common confi...

Page 34: ...en the Dielectric Withstand tester and the device under test if the device has a turn on switch it has to be in the ON position Figure 14 Connection between HT PR and a device with 3 wire power supply...

Page 35: ...2 connector Return Connector Isolation check A B A to B A and B C Conductors to isolated material Note in this mode the Ground check switch has to be set in the OFF position Test results Hipot Pass If...

Page 36: ...ce West USA is available Phone 800 748 6224 Hours 8 30 AM 4 30 PM Pacific Time Also available on our web site at www compwest com Contact Compliance West USA 650 Gateway Center Way Suite D San Diego C...

Page 37: ...ns given in Section 1 A three inch piece of approx 18 AWG insulated hookup wire with each end stripped back and a lead with a banana plug on one end are required to conduct the performance test The te...

Page 38: ...omatic hydrocarbons or chlorinated solvents for cleaning These solutions will react with the plastic materials used in the instrument Clean the front panel and case with a mild solution of detergent a...

Page 39: ...ead Sure if not start again at step 2 above 5 While Sure is displayed on the screen you can A Press Reset to exit out of the Calibration Mode and keep all of the currently programmed calibration setti...

Page 40: ...increase the variac watching the current flowing on the DMM Adjust the variac until 10 0mA AC is displayed on the DMM and then press the Test button 8 The display will show hold 9 Wait until the displ...

Page 41: ...ly for an HT 3000PR select DC by pressing AC DC selector switch 8 Only for an HT 3000PR Press Test and confirm that the meter displays 1 5 Press Test again and wait until the display return to r1 9 Co...

Reviews: