4. Route the cable into the fully-open tray through the cable guide as shown.
Figure 15. Cable Routing for 72-Position Termination Tray
(Left Entry Only)
5. Route the cable within the tray as shown in
Figure 15
. Note that there are different
routings for cables being terminated at the front and rear of the adapters packs.
6. Secure the cables on the side and rear of the tray as shown in
Figure 15
.
Note: Before tying off the cable as shown, proceed with the next step below.
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not
look into the ends of any optical fiber. Do not look directly into the optical adapters of the adapter
packs. Exposure to invisible laser radiation may result. An optical power meter should be used to
verify active fibers. A protective cap or hood MUST be immediately placed over any radiating
adapter or optical fiber connector to avoid the potential of dangerous amounts of radiation
exposure. This practice also prevents dirt particles from entering the adapter or connector.
Note: Always clean and inspect connectors and adapters before mating them. For
guidelines, refer to the connector cleaning instructions, ADCP-90-159.
19994-C
LOOP FIBER
S
ONE
TIME AROUND
S
POOL A
S
S
HOWN
S
ECURE
S
UBUNIT TO
BRACKET
LIGHTLY
S
ECURE
FIBER TO DRAWER
WITH VELCRO
U
S
ING
S
LOT
S
IN DRAWER
RIBBON
CABLE
FANOUT
POINT
ADAPTER PO
S
ITION
67 THROUGH 72
(67 ON TOP, 72 ON BOTTOM)
ADAPTER PO
S
ITION
1 THROUGH 6
(1 ON TOP, 6 ON BOTTOM)
WAX LACING TIE POINT
FOR 900 MICRON
S
UBUNIT