![ComAp InteliVision 8 Manual Download Page 93](http://html.mh-extra.com/html/comap/intelivision-8/intelivision-8_manual_2638970093.webp)
InteliVision 8
93
Name of test
Procedure
Notes
External Power supply
EN 61000-4-11
Power supply variation
EN 61000-4-11
Low temperature
EN 60068-2-1, Ab, Ad
-20°C/ 16h
Cyclic damp heat test
EN 60068-2-30, Db
Dry heat
EN 60068-2-2, Ab, Ad
70°C/ 16h
Sinusoidal vibration
EN 60068-2-6 test Fc
5Hz - 25Hz/ ±1,6mm; 25Hz - 100Hz / 4g
Flammability
EN 60695-11-5:05
High Voltage
Germanische Lloyd spec.,
VI-Part 7, §14
Power supply terminals against box: Uef. 572 V;
duration 1 min
Insulation resistance
Germanische Lloyd spec.,
VI-Part 7, §13
Electrostatic discharge
EN 61000-4-2
6kV contact discharge; 8kV air discharge
Radiated elmag. field
immunity
EN 61000-4-3
Fast low energy
transients/bursts
EN 61000-4-4
Slow high energy
transient/surges
EN 61000-4-5