InteliATS
NT
PWR, SW version 2.5, ©ComAp
– May 2015
52
IA-NT- PWR-2.5-Reference Guide.pdf
Mode MAN
The output is closed, if MAN Mode is selected.
Mode AUT
The output is closed, if AUT Mode is selected.
Mode TEST
The output is closed, if TEST mode is selected.
Exerc Timer 1
Output activates when Timer 1 is active. See setpoint
Timer1..2Function [No Func/TEST/TEST
OnLd/MFail Blk/Mode OFF/Rem Trans]
for details.
Exerc Timer 2
Output activates when Timer 2 is active. See setpoint
Timer1..2Function [No Func/TEST/TEST
OnLd/MFail Blk/Mode OFF/Rem Trans]
for details.
Not In AUT
Output activates when the controller is not in AUT mode.
Neutral Pos
Switches ATS switch to its neutral position. It is a complement to the MCB and GCB Close/Open
binary outputs and it switches the ATS switch to its neutral position by applying voltage level change
(log. 0/ log. 1).
MCB Close/Open output switches the ATS three way switch to the position I.
GCB Close/Open output switches the ATS three way switch to the position II.
Neutral Pos output switches the ATS three way switch to the position 0 (middle).
The resulting behavior of the ATS output differs depending on the priority of the inputs of the particular
type of the ATS switch.
If the neutral position input of the switch has the highest priority it overrides the current position of the
switch and forces the switch to the neutral position.
Neutral Coil
Activates the neutral position coil of the ATS switch. It is
a complement to the MCB and GCB ON Coil
and it switches the ATS switch to its neutral position by applying a voltage pulse.
MCB ON Coil output switches the ATS three way switch to the position I.
GCB ON Coil output switches the ATS three way switch to the position II.
Neutral Coil output switches the ATS three way switch to the position 0 (middle).
Power Switch
This switch is assigned to the gen-set active power. The setpoints
PowerSwitch ON [kW]
and
PowerSwitch OFF [kW]
for on and off level adjustment are located in the setpoint group
Engine
Params
. Typical usage for this binary output can be switching of dummy load. The output behaves