InteliATS
NT
PWR, SW version 2.5, ©ComAp
– May 2015
31
IA-NT- PWR-2.5-Reference Guide.pdf
AMF using two-position ATS with feedback
G
IA-NT
3x
3
x
U
M
3
x
U
G
3
x
I G
3x
T
MCB FEEDBACK
GCB FEEDBACK
3x
MCB CLOSE/OPEN
GCB CLOSE/OPEN
BO
BI
K3
ATS on "II" position
LOAD
ATS
3x
ATS
I
II
Specification
Automatic remote gen-set start when the mains fails (AUT mode)
Two-position ATS control with feedback
Break transfer on mains failure
Break return on mains return (Load reclosing)
Test mode (set running and waiting for mains failure)
Hardware requirements
1x
IA-NT PWR
Setpoints
MCB Logic = “CLOSE-ON”