InteliATS
NT
PWR, SW version 2.5, ©ComAp
– May 2015
105
IA-NT- PWR-2.5-Reference Guide.pdf
Alternative connection using external RS232-RS422/485 converter:
Recommend external converter:
ADVANTECH
– ADAM 4520: RS232 to RS422/485 converter, DIN rail, automatic RS485 bus
supervision, no external data flow control signals, galvanic isolated, baud rate 38400 or 56000 bps.
Any connected RS 232 to RS 422/485 converter has to be set to passive DSR signal (when DSR
connected) after switch on.
Function description
Remote display IL-NT-RD works as remote display and control of the master InteliATS
NT
, InteliLite
NT
or
InteliDrive Lite controller. It is supposed and highly recommended that both, remote display and
master are using the same HW type and model of controller. Another types and models of master and
remote display are not supported nor tested. All remote display’s LEDs show the same state as
corresponding LEDs on master controller. Front panel buttons on both controllers work in the same
way. Genset/Engine can be controlled from remote display as well as from master controller. User can
switch screens, set password, change setpoints and view history records.
All IL-NT-RD screens Init, Measure, Setpoints and History display the same data like in the master
controller.
Master device is always able to work without connected Remote display.
Interruption of the serial line between master device and Remote display has no effect to the master
controller.
If the serial line between master device and remote display is interrupted, or communication cannot be
established, remote display shows it’s Init screen and message “Trying” and all LED’s are off.
Once remote display finds compatible master it shows “Preparing” and downloads configuration table
from master controller.
After the configuration from master is downloaded remote display jump to master controllers Init
screen and all LEDs and blinking.
It is possible to switch to remote displays Init screen to check it’s version and serial number of used
controller and communication status by pressing PAGE button for 3 seconds.
SW compatibility
IL-NT-RD sw. version 1.0 is compatible with masters SW:
All InteliATS
NT
standard software from ver. 1.0
All InteliLite
NT
standard software from ver. 1.1
All ID-Lite standard software from ver. 1.0
Chosen InteliATS
NT
, InteliLite
NT
and ID-Lite customer branches
Some of the future InteliATS
NT
, InteliLite
NT
, ID-Lite versions may require upgrade of the IL-NT-RD