Installation
2-8
750-437
Q Series Full Modulation
2.10 — Combustion Air Inlet Orifice Plate Installation
The Q burner size 6 and 8 use air-inlet-orifice plates to limit combustion air to the maximum firing rate needed
with respect to an application. The Q6 has a maximum rating of 1,500,000 BTU/HR. When used for the
maximum rate an air-inlet-orifice plate is not used. The same is true of the Q8 when used at its maximum rating
of 2,500,000 BTU/HR. For other firing rates, the chart below identifies the air-inlet orifice plate required:
Remove the existing (6) bolts from the fan-assembly inlet collar and air-pressure sensing line. Align the plate and
air-inlet sensing line then replace the (6) bolts. Use a medium thread locker such as Loctite Blue to assure
secure retention.
TABLE 2- 1.
Air Inlet Orifice Plate Application
Model
Burner BTU/HR rating
Air inlet Plate Part Number
Orifice Diameter (in)
Q6
550,000
059-11448-000
1.50
750,000
059-11449-000
1.80
1,000,000
059-11450-000
2.25
1,300,000
059-11452-000
2.95
1,500,000
no orifice plate used
-
Q8
1,750,000
059-11457-000
3.45
2,000,000
059-11458-000
3.80
2,500,000
no orifice plate used
-
FIGURE 2-8.
Inlet Orifice Plate Installation