750-437
Q Series Full Modulation
6-17
Troubleshooting
121
Any #
Internal error EEPROM access
Reset the fault and check to make sure the last parameter that was viewed / changed is set
properly. Restore the parameter set if possible. If the fault occurs continuously, replace the
LMV3.
122
Any #
Internal error EEPROM access
123
Any #
Internal error EEPROM access
124
Any #
Internal error EEPROM access
125
Any #
Internal error EEPROM read access
Reset the fault and check to make sure the last parameter that was viewed / changed is set
properly. If the fault occurs continuously, replace the LMV3.
126
Any #
Internal error EEPROM write access
127
Any #
Internal error EEPROM access
Reset the fault and check to make sure the last parameter that was viewed / changed is set
properly. Restore the parameter set if possible. If the fault occurs continuously, replace the
LMV3.
128
0
Internal error EEPROM access -
synchronization during initialization
If the fault occurs continuously, replace the LMV3.
129
Any #
Internal error EEPROM access - command
synchronization
Reset the fault and check to make sure the last parameter that was viewed / changed is set
properly. If the fault occurs continuously, replace the LMV3.
130
Any #
Internal error EEPROM access - timeout
131
Any #
Internal error EEPROM access - page on
abort
132
Any #
Internal error EEPROM register
initialization
If the fault occurs continuously, replace the LMV3.
133
Any #
Internal error EEPROM access - request
synchronization
Reset the fault and check to make sure the last parameter that was viewed / changed is set
properly. If the fault occurs continuously, replace the LMV3.
134
Any #
Internal error EEPROM access - request
synchronization
135
Any #
Internal error EEPROM access - request
synchronization
136
Any #
Restore
No fault: A restore was started via parameter 050. New LMV3s require a reset after a
restore. Reset the LMV3.
1
Restore started - for further diagnostic
codes, refer to error code 137
Error
Code Diag. Code Description
Corrective Action
Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
Summary of Contents for ProFire Q Series
Page 2: ......
Page 18: ...Introduction 1 8 750 437 Q Series Full Modulation...
Page 28: ...Installation 2 10 750 437 Q Series Full Modulation...
Page 50: ...Operation 3 22 750 437 Q Series Full Modulation...
Page 82: ...Troubleshooting 6 24 750 437 Q Series Full Modulation...
Page 87: ......
Page 88: ......