Operation
3-12
750-437
Q Series Full Modulation
Press
(
enter)
to accept the value. The display cursor position advances to accept the second character:
Press
(-)
then
(
enter)
four more times to enter “Y” five times; the sixth underscore will be flashing following
entry of the fifth “Y”:
Press
(
enter)
to enter the password. A successful login will briefly display
{PArA}
followed by:
{400: SEt}
“400” flashing
An incorrect entry attempt will display:
{Error}
then
{OFF}
If the attempt fails, repeat the steps from the beginning of this section.
Note:
The following conditions will exit you from AZL parameter entry (log out):
•Power to the LMV3 is disconnected or cycled.
•The AZL is unplugged from the LMV3.
•Timeout (AZL inactive for a time period greater than parameter 127 setting).
•While in a parameter group with
{X00: SEt}
(X = 1,2,3 etc.), hold
(ESC / - & +)
until
{CLr CodE}
displays.
To regain access after a log out, repeat the password entry steps.