background image

 

 

XPO

TM

 

Ultra Low NOx Indirect Burner

 

超低排放氮氧化物間接燃燒器

 

 
 

 

 

 

 

 

 
 
 

 

Low temperature burner for use with clean fuel gases 

使用清潔燃氣的低溫燃燒器

 

 

 

Single digit NOx emissions at 30% excess air 

 

30%

的過剩空氣下,氮氧化物排放只有個位數

 

 

 

High efficiency with low excess air requirements 

低過剩空氣要求下,高效率

 

 

 

Capacities up to 2250KW. 

高達

 

2250KW 

的燃燒效率

 

 

 

For use in indirect fired solution backed heaters 

用作間接液體加熱

 

 
 

 

 

 

08092018 

Summary of Contents for XPO 1PB

Page 1: ...se with clean fuel gases 使用清潔燃氣的低溫燃燒器 Single digit NOx emissions at 30 excess air 在 30 的過剩空氣下 氮氧化物排放只有個位數 High efficiency with low excess air requirements 低過剩空氣要求下 高效率 Capacities up to 2250KW 高達 2250KW 的燃燒效率 For use in indirect fired solution backed heaters 用作間接液體加熱 1 08092018 ...

Page 2: ...ergrated withflame supervision safetyinterlockand flowcontrolfunction withuser freiendlyinterfaceforoperator TheStandard configuration include 1 IntergratedDoublesafetyshut offvalvewithpressureregulating funciton 2 SLATE burnercontrolunitwith electricalparralactuatorwithair dampler gasBV 3 UVsensor 4 Gashigh lowpressureswitch pressureswitchforvalvetightness test airpressureswitch 5 packagebloweror...

Page 3: ...11 4 5 5 助燃風壓力 mbar 30 28 40 40 40 56 40 40 燃燒管外徑 mm 152 152 152 203 203 203 152 203 鍋爐燃燒管內徑 mm 355 457 406 560 457 610 560 812 560 864 560 914 457 610 560 864 燃氣壓力 mbar 100 350 100 350 100 350 100 350 150 350 200 350 100 350 150 350 爐膛背壓 mbar 適用鍋爐 熱水或蒸汽 噸 小時 0 0 5 W S 0 5 W S 1 0 W S 1 5 W S 2 W S 2 5 W S 1 0 W S 2 W S 5 0 5 W 0 45 S 0 5 W S 1 0 W S 1 5 W 1 47 S 2 W S 2 5 W 2 4 S 1 0 W S 2 W S 7 ...

Page 4: ...4 08092018 III Dimensions for installaiton 安裝尺寸 XPO 1 2 3PB XPO 4 5PB XPO 3 5PAK ...

Page 5: ...sk layout drawing from HTS sales 高度和長度根據佈置的不同會有變化 請參照 Honeywell 單獨提供的組裝 圖尺寸 D E 45 45 45 30 30 30 399 6 521 F 457 457 457 711 711 711 321 410 G 420 420 420 641 641 641 281 360 H 160 160 160 209 209 209 160 1 209 I 23 23 23 23 23 23 220 2 288 J 16 16 16 16 16 23 17 5 17 5 K note 159 159 159 216 216 216 159 1 216 Note The flange for XPO1 2 3 and 4 5 are different Both on bolts position and quantity ...

Page 6: ... greater with minimum thermal conductivity of 12 W m K at 980 C 1 XPO burner XPO 燃燒器 2 Mountingflange 固定法蘭 3 Unit wall 單元牆 4 Liquid solution 液體溶液 5 Fire tube 煙管 6 Burner blast tube 燃燒器排氣管 7 Non cooled fire tube wall 非冷卻煙管壁 8 Customer supplied insulation 客戶提供的隔熱材料 All non liquid cooled surfaces must be insulatedas shown above 所有非液體冷卻面必須按如圖所示方式進行隔熱 1 Blast tube 2 Liquid solution 3 Fire tube 4 152 mm...

Page 7: ...is manual should be made to the address on the cover sheet 與此手冊內容有關的問題請參照首頁上的位址進行詢問 All work and operation of the plant should be carried out by trained qualified operators tradesmen or engineers 車間的所有工作和操作必須由培訓過或有資格的操作員 技術工人或工程師完成 Before undertaking maintenance work on any item of the equipment it must be made safe 在對設備任何專案進行維修工作前 必須保證設備處於安全狀態 Fuel supply should be manually isolated and fuel isol...

Page 8: ...n insure the following 安裝過程中確保以下要求 All valve handles can rotate to full open or full close position 所有閥門手柄能夠開關自如 All elements are piped in the proper flow direction 所有部件安裝方向正確 Interconnecting piping should be installed in such a manner that undue stress will not be imposed on the Main Gas Train 連接管道不應對燃氣盤產生應力 Insure the piping system is pressure tested and blown clean before final connection to an...

Page 9: ...th burner and process operating normally and satisfactorily optimize and record operating range parameters including 在燃燒器運行正常情況下 完善和記錄以下工作參數 i Pressures 壓力 ii Flows 流量 iii Temperatures 溫度 iv Settings 設置 v Combustion analysis 燃燒廢氣分析 3 To ensure continuing trouble free operation the following areas should be addressed at the intervals shown 為了保證連續無故障運行 以部件見需在顯示的時間間隔中進行週期性的檢查 INTERVAL 時間間隔 1 Months 1...

Page 10: ...滑油 詳細參照部 件 部分 X Clean Burner Working Surfaces 清潔燃燒器工作表面 X Compare Gas Pressure At Burner Inlet With Commissioning Data 將燃燒器進氣口處燃氣壓力和調試資料 進 行比較 X Confirm Correct Operation Of Pressure Switches 確認壓力開關正確運行 X Replace Spark Plug 更換火花塞 X Replace UV Scanner Flame Rod 更換紫外線探頭 火焰棒 X Check Clean Air Gas Ports In Pilot Burner Casting 檢查和清潔點火管路燃燒器鑄件上的空 氣 和燃氣口 X Clean Seats on Pilot Main Gas Safety Shut Off Va...

Page 11: ...11 08092018 清潔點火管路和主燃氣管路上燃氣安全 截止閥的底座 Check Gas Pipe Work Joints For Tightness 檢查燃氣管介面處的氣密性 X ...

Page 12: ... at pilot 點小火失敗 燃燒器在點小火 時 報警 a No gas 沒有燃氣 b Too much gas 燃氣過多 c Pilot valve not open 小火閥未打開 a Restore gas supply 恢復燃氣供應 b Adjust gas pilot rate 調節燃氣比率 c Change valve 替換閥門 d Clear open circuit 修復斷路的線路 Pilot fails to light Burner locks out at pilot 點火失敗 燃燒器在點小火時 報 警 a UV Scanner Flame Rod not detecting flame UV探頭 火焰棒探測不到火 焰 b Bad ground 接地回路斷開 a Reposition UV Scanner Flame Rod 重新放置 UV 探頭 火焰棒 b Repa...

Page 13: ... 高 低燃氣壓力開關失靈 b Process pressure switch faulty 工藝空氣壓力開關失靈 c Process pressure low 工程空氣壓力過低 d Interlock circuit broken 聯 鎖回路斷路 a Replace gas pressure switch 更換燃氣壓力開關 b Check process fan 檢查工藝風機 c Reinstate interlock 修理聯鎖裝置 Main flame extinguishes during steady fire Burner locks out at normal run 在火焰穩定期間 主火焰熄 滅 燃燒器在正常運行時報警 切 斷 a Loss of gas supply 燃氣供應不足 b Loss of combustion air 燃 燒空氣不足 c Failure of fl...

Page 14: ...USE 故障原因 REMEDY 補救措施 Heat output not maintained 不能持續供熱 a Gas pressure fall 燃氣壓力下降 b Burner head dirty 燃燒器頂端髒汙 a Restore gas pressure 恢復燃氣壓力 b Clean burner 清潔燃燒器 瞭解更多資訊 欲瞭解更多霍尼韋爾熱能解決方案的產品及服務 請訪問 ThermalSolutions honeywell com 或與 您當地的銷售代表聯絡 ...