Step 19
Save the configuration in the startup configuration by using the
copy running-config startup-config vdc-all
command.
switch(config)#
copy running-config startup-config vdc-all
Nondisruptive Migration from Supervisor 2E Modules
(N77-SUP2E) to Supervisor 3E Modules (N77-SUP3E)
Nondisruptive Migration from Supervisor 2E Modules (N77-SUP2E) to Supervisor 3E Modules (N77-SUP3E)
has the following limitations:
• Do not change any configuration settings or network connections during the upgrade.
• Configuration mode is blocked during the migration procedure to prevent any changes.
• You cannot press C to abort the migration procedure until 45 minutes have elapsed since the
migrate sup kickstart <sup3-kickstart-image> system <sup3-system-image>
command has been used.
• Before you initiate the migration procedure, you must first remove QoS policies and ACLs from interfaces
that are in the down state. The clear inactive-config qos command, that clears inactive configuration,
will delete the port channel policies even if one of the ports in a port channel has inactive policies.
Guidelines for manual policy removal:
• During manual removal, when the interface is part of a port channel, remove the policy map or
access list from the port channel or remove the interface from the port channel before initiating the
migration procedure.
• For all other interface types, please remove the policy map or access list from the interface.
• The
migrate sup kickstart <sup3-kickstart-image> system <sup3-system-image>
command that is
used to initiate the non-disruptive migration process is only available in global config mode.
• Ensure that the Supervisor-3E module has not been inserted in the standby slot before using the
migrate
sup kickstart <sup3-kickstart-image> system <sup3-system-image>
command. If the supervisor-3E
module has already been inserted in the standby slot, the migration process will be aborted and the
supervisor-3E module will be powered down.
• Do not reload or manually insert or remove any I/O or fabric module after using the
migrate sup kickstart
<sup3-kickstart-image> system <sup3-system-image>
command. Any removal or insertion of I/O or
fabric modules has to be done before initiating the migration process or after the migration is completed.
• Do not remove or insert any Fabric Extender (FEX) modules during migration.
• Insert the standby Supervisor-3E module into the chassis only when you are prompted to insert the
Supervisor-3E module during migration by a message on the system console.
• After the Supervisor-3E module has been inserted during the migration process, do not remove or manually
reload the standby Supervisor-3E module.
• Do not insert or remove any transceivers from any modules while the migration is in progress.
• Do not remove any power supply modules or fan modules during the migration process.
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
93
OL-30452-01.
Installing or Replacing Modules, Fan Trays, and Power Supplies
Nondisruptive Migration from Supervisor 2E Modules (N77-SUP2E) to Supervisor 3E Modules (N77-SUP3E)