Result
Power Source
Redundancy
Input Source
Redundancy
Output for Power Supplies
Power
Rqmnt
Scenario
Res.
Avail.
Res.
Avail.
4
3
2
1
Available
power
for both
redundancies
exceeds
the
switch
requirements,
so the
entire
switch
can
power
up.
1.45
kW
4.35
kW
2.9 kW
2.9 kW
1.45
kW
1.45
kW
1.45
kW
1.45
kW
2.8 kW
2
Configuring the Power Mode
You can configure the power supply mode by using the
power redundancy-mode
command.
To display the current power supply configuration, use the
show environment power
command.
Note
Step 1
Start the configuration mode by entering the
configure terminal
command.
Example:
switch#
configure terminal
switch(config)#
Step 2
Specify one of the following power modes by entering the
power redundancy-mode mode
command:
• For combined mode, include the
combined
keyword.
• For power supply redundancy mode, include the
ps-redundant
keyword.
• For input source redundancy mode, include the
insrc_redundant
keyword.
• For full redundancy mode, include the
redundant
keyword.
Example:
switch(config)#
power redundancy-mode redundant
switch(config)#
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
77
OL-30452-01.
Managing the Switch
Configuring the Power Mode