The following example shows the syslogs displaying the fan tray maintenance mode being cancelled after the
post-cool period of 4 minutes is completed:
2017 Apr 3 16:20:08 SWITCH %PLATFORM-2-PFM_CRITICAL: FAN_MAINTENANCE_MODE: system is ready
for fan-removal.
2017 Apr 3 16:21:07 SWITCH %PLATFORM-2-FAN_REMOVED: Fan module 1(Serial number NCV2108V017)
Fan1(sys_fan1) removed
2017 Apr 3 16:21:08 SWITCH %PLATFORM-6-PFM_INFO: Fan Zone 1 : Fan Speed will change from
85.10(0xd9) to 74.90(0xbf)
2017 Apr 3 16:21:11 SWITCH %PLATFORM-1-PFM_ALERT: System shutdown in 3 days 0 hours 0 mins
0 seconds due to fan policy __pfm_
fanabsent_any_singlefan for fan1
2017 Apr 3 16:23:09 SWITCH %PLATFORM-6-PFM_INFO: Fan Zone 1 : Fan Speed will change from
74.90(0xbf) to 85.10(0xd9)
2017 Apr 3 16:25:09 SWITCH %PLATFORM-6-PFM_INFO: Fan Zone 1 : Fan Speed will change from
85.10(0xd9) to 100.00(0xff)
2017 Apr 3 16:25:33 SWITCH %PLATFORM-5-FAN_DETECT: Fan module 1(Serial number NCV2108V017)
Fan1(sys_fan1) detected
2017 Apr 3 16:25:33 SWITCH %PLATFORM-5-FAN_STATUS: Fan module 1(Serial number NCV2108V017)
Fan1(sys_fan1) current-status is F
AN_OK
2017 Apr 3 16:25:33 SWITCH %PLATFORM-2-FANMOD_FAN_OK: Fan module 1(Fan1(sys_fan1) fan) ok
2017 Apr 3 16:25:33 SWITCH %PLATFORM-6-PFM_INFO: Fan Zone 1 : Fan Speed will change from
100.00(0xff) to 45.88(0x75)
2017 Apr 3 16:25:33 SWITCH %PLATFORM-2-PFM_CRITICAL: FAN_MAINTENANCE_MODE_CANCELLED:
Reason(s): Temperature alarm: No, Superv
isor hot-inlet: No, Absent fans count: 0, Precool period completed: N/A, Postcool period
completed: Yes, Total maint. duratio
n: 564 seconds
If you need to remove the fan tray to replace a fabric module, see
Installing or Replacing a Fabric Module,
The fan tray displays the fabric module LEDs so that you can see the status of the two fabric modules installed
behind that fan tray.
Note
Before you begin
• You must follow ESD protocols, including the following:
• You must wear a grounded ESD wristband (or other personal grounding device) whenever you
handle the electronic modules outside the grounded chassis.
• You must carry electronic modules by only their covered edges or handles. Do not touch their
electronic components.
• Whenever a module is outside a grounded chassis, place it flat on an antistatic surface or in an
antistatic bag. Never lean the module on anything nor place anything else on top of the module nor
lean anything on the module.
• Verify that the chassis is grounded.
• Verify that you have the following tools and equipment:
• ESD wrist strap (or other personal grounding device)
• Number 1 Phillips torque screwdriver
Cisco Nexus 7710 Switch Site Preparation and Hardware Installation Guide
OL-30452-01.
118
Installing or Replacing Modules, Fan Trays, and Power Supplies
Replacing a Fan Tray