6-14
Cisco 1240 Connected Grid Router Hardware Installation Guide
OL-26223-04
Chapter 6 Installing the Router
Additional Router Connections
Cable Glands Description
Figure 6-8
Cable Glands, Assembled
Figure 6-9
Cable Gland Components
Cable Requirements
Cables used with the cable glands should meet the following criteria:
•
Outdoor-rated
•
UV-stabilized
•
Diameter of 0.20-0.35 inches (5.08-8.89 mm)
Caution
Cables must be a minimum of 0.20 in. in diameter to create an adequate seal within the cable glands.
Using smaller cables could result in an inadequate seal and therefore expose the router interior to
environmental elements.
300596
Item
Name
Description
1
Adapter
Connects directly to the chassis cable port on the router.
2
Grommet
Secures the split gasket over the cable.
3
Split gasket
Fits over the cable and creates an liquid-tight seal inside the glands.
4
Cap
Fits over gasket-and-cable assembly and connects it to the chassis cable port.
300591
1
2
3
4