85
Instruction Manual
MYeBOX 150 - MYeBOX 1500
11�- TECHNICAL FEATURES
Power supply (AC power supply adaptor)
Input
Rated voltage
100 ... 240 V
~
Frequency
47 ... 63 Hz
Consumption
MYeBOX 150
MYeBOX 1500
22... 28 VA
25... 31 VA
Installation category
CAT II 300 V
Output
Rated voltage
9 V
Consumption
MYeBOX 150
MYeBOX 1500
18 W
20 W
Voltage measurement circuit
Voltage measurement margin
10 ...600 V ~
(PH-N)
Frequency measurement margin
42.5 ... 69 Hz
Input impedance
2.4 M
Ω
Minimum measurement voltage (Vstart)
10 V ~
Maximum voltage input consumption
0.15 VA
Installation category
CAT III 600 V
Current measurement circuit
Type of clamp / Transformer
Phase and neutral current measurement
Clamps: CPG-5, CPG-100, CPRG-500, CPRG-1000,
CPG-200/2000, FLEX-Rxxx,
Transformer with 250 mA or 333 mV output
Leakage current measurement
(
MYeBOX 1500
model)
CFG-5, CFG-10, WG type transformers
Nominal current (In)
Current measurement margin
1 ... 200 In %
Maximum current, impulse < 1s
3*In A
Minimum measurement current(Istart)
Maximum current input consumption
0.0004 VA
Installation category
CAT III 600 V
Frequency of sampling
MYeBOX 150
50 Hz
60 Hz
44.8 kHz
53.76 kHz
MYeBOX 1500
57.6 kHz
69.12 kHz
Accuracy of measurements
(19)
Voltage measurement (Ph-N)
(20)
Class 0.2 (10 ...600 V~) (IEC 61557-12)
Clase A (23 ...345 V~) (IEC 61000-4-30)
Current measurement
Class 0.2 (1%...200% In) (IEC 61557-12)
Measurement of active and apparent power
(Vn 230/110 V~)
Class 0.5 ± 1 digit (IEC 61557-12)
Reactive power measurement
(Vn 230/110 V~)
Class 1 ± 1 digit (IEC 61557-12)
Active energy measurement
Class 0.5S (IEC 62053-22)
Reactive energy measurement
Class 1 (IEC 62053-23)
Frequency measurement
Clase A ( 42.5 ... 69 Hz) (IEC 61000-4-30)
Summary of Contents for MYeBOX 150
Page 2: ...2 MYeBOX 150 MYeBOX 1500 Instruction Manual...
Page 90: ...90 MYeBOX 150 MYeBOX 1500 Instruction Manual 14 CE CERTIFICATE...
Page 91: ...91 Instruction Manual MYeBOX 150 MYeBOX 1500...
Page 92: ...92 MYeBOX 150 MYeBOX 1500 Instruction Manual...