Table 20 (Continued) :
List of variables that can be included in the STD file
Variables
Unit
Phases
L1-L2-L3
N
Total
III
Record
Period
(15)
Direct current
-
5 min
Inverse current
-
5 min
Current maximum demand
A
15 min
Active power maximum demand
kW
15 min
Aparent power maximum demand
kVA
15 min
Variables
Unit
Tariff T1 - T2
Record
Period
(5)
Cost
COST
5 min
CO
2
Emissions
kgCO
2
5 min
(15)
Default recording period.
The variable recording period can be configured by the user.
Note:
Only 32 variables can be saved at once with a recording period of 1 second.
For example:
Table 21:Example of saving 32 variables with a recording period of 1 second�
Variables
L1
L2
L3
Total III
Phase-neutral voltage
1
1
1
1
Phase-phase voltage
1
1
1
1
Current
1
1
1
1
Active power
1
1
1
1
Inductive and Capacitive reactive power
2
2
2
2
Power factor
1
1
1
1
Frequency
1
Flicker
1
1
1
Total off variables
32
Some of the variables in the
STD
file require an explanation:
Instant Flicker and PST Flicker:
The device will record the instant Flicker and the value obtained during the recording period
(
Flicker PST
). The
PLT
value is calculated by the Mobil applications.
Harmonics:
MYeBOX
measures and records the average individual harmonic distortion up to the 50th har-
monic, and the voltage and current THD value up to the 40th harmonic. Each record corre-
sponds to a block of 10 cycles, within the recording period.
Unbalance:
The device calculates the coefficients for asymmetry and unbalance in the voltages and cur
-
rents of the three-phase system.