Table 16 (Continued): LED description, MYeBOX 1500�
LED
Description
U1
U2
U3
UN
URef
Power off
No voltage at the corresponding input. (U1: L1, U2: L2, U3: L3, UN: LN,
URef: Reference voltage)
Power on
Voltage at the corresponding input. (U1: L1, U2: L2, U3: L3, UN: LN, URef:
Reference voltage)
Blinking lights U1, U2 and U3 (1 s)
L1-L2-L3 phase sequence error
I1
I2
I3
Power off
Clamp not connected (I1: L1, I2: L2, I3: L3)
Power on
Clamp connected (I1: L1, I2: L2, I3: L3)
Blinking lights (1 s)
Negative power or
cos
< ± 0.6
IN
ILeak
Power off
Clamp not connected (IN: LN, ILeak: Leakage current)
Power on
Clamp connected (IN: LN, ILeak: Leakage current)
4.6.-
INPUTS (
MYeBOX 1500
model)
The
MYeBOX 1500
has two digital inputs
grammed through the mobile application.
Note:
The digital inputs must be connected to SELV (Safety Extra Low Voltage).
4.7.- OUTPUTS (
MYeBOX 1500
model)
The device has two transistor digital outputs (terminals 15, 16 and 17 of
) that can be
programmed through the mobile application to function as alarms.