16
MYeBOX 150 - MYeBOX 1500
Instruction Manual
3.5.- VOLTAGE CABLES
To measure voltage, you must use 600 V CAT III double-insulated connection cables.
The
Kit B_MYeBOX 150
and
Kit B_MYeBOX 1500
kits come with the necessary cables:
- UL 600 V CAT III double-insulated voltage cables, or higher.
- UL 600 V CAT III crocodile clamps
Coloured markers are included with the devices to identify the measuring channels according
to each country's standard.
Table 4: Cable colours: European (IEC 60445 :2010)�
Phase
Cable colour
L1
Brown
L2
Black
L3
Grey
N
Light blue
I Leak
Maroon
Earth
Green / Yellow
3.6.- CURRENT CLAMPS
The current may be measured using current clamps or transformer clamps.
The device automatically recognises the clamps that are connected to it and shows the neces-
sary parameters in the setup menu. (“
6.1.- SETUP MENU: MEASURE SETUP
Using clamps is necessary
IEC 61010-2-032
.
Phase and neutral current measurement:
Table 5: Clamps and transformers for measuring the phase current and the neutral current�
Type
Scale
Measurement range
Accuracy
(1)
CPG-5
-
0.05 ... 5 A
0.2% (3 % ... 120% In)
CPG-100
-
1 ... 100 A
0.2% (3 % ... 120% In)
CPRG-500
-
1 ... 500 A
0.2% (3 % ... 120% In)
CPRG-1000
-
1 ... 1000 A
0.2% (3 % ... 120% In)
CPG-200/2000
LOW
1 ... 200 A
0.2% (3 % ... 120% In)
HI
10 ... 2000 A
0.2% (3 % ... 120% In)
FLEX-Rxxx
LOW
100 A
1% (10 % ... 200% In)
MEDIUM
1000 A
1% (10 % ... 200% In)
HI
10000 A
1% (10 % ... 200% In)
Transformer ���/ 0�333V
-
1% ... 200% In
1% (1% ... 19% In)
0.5% (20% ... 120% In)