EN-
25
POWERCIAT LX ST/HE/XE
4.5 - Electrical data, optional hydraulic module
The pumps that are factory-installed in these units comply with the European Ecodesign directive ErP. The additional
electrical data required
(1)
is as follows:
Low pressure single and dual pump motors for LX units
No.
(2)
description
(3)
0808
0908
1008
1108
1358
1528
1
Nominal efficiency at full load and nominal voltage
%
86,7
86,7
87,2
88,1
89,4
89,4
Nominal efficiency at 75% full load and nominal voltage
%
87,0
87,0
86,9
88,0
88,9
88,9
Nominal efficiency at 50% full load and nominal voltage
%
85,5
85,5
84,5
86,1
86,7
86,7
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the
time of incorporation. Please refer to the motor nameplates.
4
Company name or trademark, commercial registration number and head office
of manufacturer
-
Same as above
5
Product model number
-
Same as above
6
Number of motor poles
-
2
7-1 Nominal shaft power output at full load and nominal voltage (400 V)
kW
2,2
2,2
3,0
4,0
5,5
5,5
7-2 Maximum input power (400V)
(4)
kW
2,54
2,54
3,44
4,54
6,15
6,15
8
Nominal input frequency
Hz
50
9-1 Nominal voltage
V
3*400
9-2 Maximum current drawn (400V)
(5)
A
4,2
4,2
5,5
7,4
9,7
9,7
10 Nominal speed
r/s - r/min 48 - 2900 48 - 2900 49 - 2915 49 - 2915 49 - 2930 49 - 2930
11 product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the
specific conditions given in the CIAT selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
Low pressure single and dual pump motors for LX units
No.
(2)
description
(3)
0808
0908
1008
1108
1358
1528
1
Nominal efficiency at full load and nominal voltage
%
88,1
89,4
89,4
90,1
91,3
91,3
Nominal efficiency at 75% full load and nominal voltage
%
88,0
88,9
88,9
89,7
91,4
91,4
Nominal efficiency at 50% full load and nominal voltage
%
86,1
86,7
86,7
87,9
90,3
90,3
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the
time of incorporation. Please refer to the motor nameplates.
4
Company name or trademark, commercial registration number and head office
of manufacturer
-
Same as above
5
Product model number
-
Same as above
6
Number of motor poles
-
2
7-1 Nominal shaft power output at full load and nominal voltage (400 V)
kW
4
5,5
5,5
7,5
11
11
7-2 Maximum input power (400V)
(4)
kW
4,5
6,2
6,2
8,3
12,0
12,0
8
Nominal input frequency
Hz
50
9-1 Nominal voltage
V
3*400
9-2 Maximum current drawn (400V)
(5)
A
7,4
9,7
9,7
13,2
18,7
18,7
10 Nominal speed
r/s - r/min 49 - 2915 49 - 2930 49 - 2930 49 - 2935 49 - 2945 49 - 2945
11 product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an
appropriate company.
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or in the
specific conditions given in the CIAT selection programs.
IV - Potentially explosive atmospheres
-
Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum unit operating current draw for a unit with hydraulic module, add the maximum unit current draw from the electrical data table to the pump
current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
4 - PHYSICAL PROPERTIES AND ELECTRICAL DATA FOR LX UNITS