4 - PHYSICAL PROPERTIES AND ELECTRICAL DATA FOR LX UNITS
4.1 - Physical properties of LX units
LX 0808 to 2158 units
LX ST-HE
0808
0908
1008
1108
1358
1528
1858
2008
2158
Sound levels
LX ST HE
Sound power
(1)
dB(A)
100
100
100
100
102
100
102
100
103
Sound pressure at 10 m
(2)
dB(A)
68
68
68
68
70
68
69
68
71
LX ST HE + low noise option
Sound power
(1)
dB(A)
94
94
95
96
96
96
98
96
98
Sound pressure at 10 m
(2)
dB(A)
62
62
63
64
64
64
66
63
65
LX ST HE + Xtra low noise option
Sound power
(1)
dB(A)
87
87
87
90
91
91
93
92
93
Sound pressure at 10 m
(2)
dB(A)
55
55
55
58
59
59
60
59
60
LX ST HE + Super low noise option
Sound power
(1)
dB(A)
-
-
-
-
89
89
91
90
91
Sound pressure at 10 m
(2)
dB(A)
-
-
-
-
57
56
58
57
59
Dimensions
LX ST HE
Length
mm
3604
3604
3604
4798
4798
5992
7186
7186
7186
Width
mm
2253
2253
2253
2253
2253
2253
2253
2253
2253
Height
mm
2297
2297
2297
2297
2297
2297
2297
2297
2297
Operating weight
(3)
LX ST standard
kg
3190
3224
3245
3834
3899
4261
4962
5093
5376
LX ST Unit + low noise option
kg
3458
3492
3513
4133
4198
4560
5293
5424
5707
LX HE standard
kg
3240
3274
3295
3934
3999
4411
5112
5293
5526
LX HE Unit + low noise option
kg
3508
3542
3563
4233
4298
4710
5443
5624
5857
Compressors
06T semi-hermetic screw, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
1
Refrigerant
(3)
R134a
Circuit A
kg
37
35
35
51
52
54
58
58
65
tCO
2
e
52,9
50,1
50,1
72,2
74,4
76,5
82,9
82,9
93,0
Circuit B
kg
38,5
36
37
36,5
37
32,5
59
62
58
tCO
2
e
55,1
51,5
52,9
52,2
52,9
46,5
84,4
88,7
82,9
Oil
Circuit A
l
20,8
20,8
20,8
23,5
23,5
23,5
23,5
23,5
27,6
Circuit B
l
20,8
20,8
20,8
20,8
20,8
20,8
23,5
23,5
23,5
Capacity control
Connect Touch, electronic expansion valve (EXV)
Minimum capacity
%
15
15
15
15
15
15
15
15
15
Air-cooled exchanger
Aluminium micro-channel coils (MCHE)
Fans
LX ST/HE
Axial type, with rotating impeller
Quantity
6
6
6
8
8
9
11
12
12
Maximum total air flow
l/s
27082,98 27082,98 27082,98 36110,64 36110,64 40624,47 49652,13 54165,96 54165,96
Maximum rotation speed
r/s
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
LX ST/HE Unit + Xtra low noise option
Maximum total air flow
l/s
20500
20500
20500
27333
27333
30750
37583
41000
41000
Maximum rotation speed
r/s
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
Exchanger
Flooded multi-pipe type
Water volume
l
58
61
61
66
70
77
79
94
98
Max. water-side operating pressure without hydraulic module
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
Hydraulic module (option)
Pump, Victaulic screen filter, relief valve, water and air vent valve, pressure sensors
Pump
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as required), single or dual
(as required)
Expansion vessel volume
l
50
50
50
50
50
80
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
Water connections with or without hydraulic module
Victaulic
®
type
Connections
inch
5 or 4
5 or 4
5 or 4
5 or 4
5 or 4
5 or 4
5
6
6
External diameter
(4)
mm
114.3 or
141.3
114.3 or
141.3
114.3 or
141.3
114.3 or
141.3
114.3 or
141.3
114.3 or
141.3
141,3
168,3
168,3
Casing paintwork
Colour code RAL 7035 & RAL 7024
(1) In dB ref=10
-12
W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured
in accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information,
calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.
(4) Depends on the number of passes on the evaporator