POWERCIAT LX ST/HE/XE
EN-
16
4 - PHYSICAL PROPERTIES AND ELECTRICAL DATA FOR LX UNITS
4.1 - Physical properties of LX units
LX 2308 to 4608 units
LX ST-HE
2308
2528
2628
3028
3428
3828
4008
4408
4608
Sound levels
LX ST-HE
Sound power
(1)
dB(A)
103
101
104
103
104
103
105
105
105
Sound pressure at 10 m
(2)
dB(A)
70
70
71
70
71
70
72
72
72
LX ST-HE + low noise option
Sound power
(1)
dB(A)
98
98
99
98
98
98
101
99
99
Sound pressure at 10 m
(2)
dB(A)
65
66
66
65
65
65
68
65
65
LX ST-HE + Xtra low noise option
Sound power
(1)
dB(A)
94
93
95
94
94
94
99
95
96
Sound pressure at 10 m
(2)
dB(A)
61
60
62
61
61
61
66
62
63
LX ST-HE + Super low noise option
Sound power
(1)
dB(A)
92
91
93
92
93
93
97
94
95
Sound pressure at 10 m
(2)
dB(A)
59
58
60
59
60
60
64
61
62
Dimensions
Standard unit
Length
mm
7186
8380
8380
9574
11962
11962
11962
11962
13157
Width
mm
2253
2253
2253
2253
2253
2253
2253
2253
2253
Height
mm
2297
2297
2297
2297
2297
2297
2297
2297
2297
Operating weight
(3)
LX ST standard
kg
5687
6072
6376
6827
8070
8211
8790
8867
9181
LX ST Unit + low noise option
kg
6018
6403
6707
7158
8441
8582
9162
9239
9553
LX HE standard
kg
5687
6072
6376
6827
8070
8211
8790
8867
9181
LX HE Unit + Low noise option
kg
6018
6403
6707
7158
8441
8582
9162
9239
9553
Compressors
06T semi-hermetic screw, 50 r/s
Circuit A
1
1
1
1
1
1
1
1
1
Circuit B
1
1
1
1
1
1
1
1
1
Refrigerant
(3)
R134a
Circuit A
kg
69
72
69
75
76
76
110
116
132
tCO
2
e
98,7
103,0
98,7
107,3
108,7
108,7
157,3
165,9
188,8
Circuit B
kg
65
63
76
79
108
120
116
124
120
tCO
2
e
93,0
90,1
108,7
113,0
154,4
171,6
165,9
177,3
171,6
Oil
Circuit A
l
27,6
27,6
27,6
27,6
27,6
27,6
36,0
36,0
36,0
Circuit B
l
23,5
23,5
27,6
27,6
36,0
36,0
36,0
36,0
36,0
Capacity control
Connect Touch, electronic expansion valve (EXV)
Minimum capacity
%
15
15
15
15
15
15
15
15
15
Air-cooled exchanger
Aluminium micro-channel coils (MCHE)
Fans
Axial type, with rotating impeller
LX ST/HE
Quantity
12
14
14
16
20
20
20
20
22
Maximum total air flow
l/s
54166
63194
63194
72221
90277
90277
90277
90277
99304
Maximum rotation speed
r/s
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
15,7
LX ST/HE Unit + Xtra low noise option
Maximum total air flow
l/s
41000
47833
47833
54667
68333
68333
68333
68333
75167
Maximum rotation speed
r/s
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
11,7
Exchanger
Flooded multi-pipe type
Water volume
l
119
119
130
140
164
174
180
189
189
Max. water-side operating pressure without hydraulic module
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
Water connections with or without hydraulic module
Victaulic
®
type
Connections
inch
6
6
6
8
6
6
6
6
6
External diameter
mm
168,3
168,3
168,3
219,1
168,3
168,3
168,3
168,3
168,3
Casing paintwork
Colour code RAL 7035 & RAL 7024
(1) In dB ref=10
-12
W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured
in accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A).
For information, calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.